beautypg.com

Technical details – Pilz PSS67 F 16DI SB-T User Manual

Page 47

background image

10-1

Operating Manual: PSS67 F 16DI SB-T

Technical Details

Electrical data

Supply voltage

24 VDC

Voltage tolerance

-15 %/+20 %

Residual ripple DC

5%

Current consumption

90 mA plus load currents taken from the
test pulse outputs

Galvanic isolation

Yes, between inputs and
SafetyBUS p

Connection

B-coded M12 connector

SafetyBUS p

Transmission rate

Max. 500 kBit/s

Cable runs

Max. 3500 m

Transmission type

Differential two-wire cable

Connection

A-coded M12 connector

Digital inputs

Number of inputs

16

Type according to 61101-2

24 VDC Type 1

Separation of supply

Yes, between inputs and SafetyBUS p

“1” Signal

+15 ... +30 VDC

“0” Signal

-3 ... +5 VDC

Input current

Typ. 3.5 mA

Input delay

< 1 ms

Pulse suppression

< 300 µs

Status indicator

Green LED

Dedicated test pulses

Number

4 (configurable in pairs as test pulse or
24 VDC output)

Output current at “1” signal

Max. 0.125 A per pin

Total load capacity

Max. 0.25 A per test pulse group

Cable runs

Between test pulse output and input
Max. 100 m