8 - 1

Operating Manual: PSS67 F 16DI SB-T

4

1

2

3

2

3

4

1

5

5

SafetyBUS p Interface

The module is connected to SafetyBUS p using a 5-pin A-coded M12
connector (X9). A 5-pin A-coded M12 socket (X10) is available to distribute
the bus signal to the other bus subscribers.

The X10 socket can also be used for bus subscriber termination.

To avoid reflection on the bus cable, the last bus subscriber must be fitted
with a terminating resistor. If the module is connected using 1:1 connection
cable, the terminating resistor is plugged into the free X10 socket . The
M12 terminator (Order no. 311 032) PSS SB M12 TERMINATOR is used
for termination via the SafetyBUS p socket.

1: Shield
2: n.c.
3: CAN_GND (white)
4: CAN_H (green)
5: CAN_L

n.c. = not connected

X9 (male connector)

X10 (female connector)

Fig. 8-1 Pin assignment of the SafetyBUS p interface