Terminal configuration, 6wiring, 2 terminal configuration – Pilz PSSu E S INC User Manual
Page 38

6.2
Terminal configuration
6
Wiring
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-4
6.2
Terminal configuration
6200
Terminal configuration
6-
][Klemmenbelegung ST INC
Base module
Terminal configuration
Screw terminals:
PSSu BP 2/16S
PSSu BP 2/16S-T
Cage clamp terminals:
PSSu BP 2/16C
PSSu BP 2/16C-T
Without C-rail:
11: Input A+
21: Input B+
31: Input C+
41: Input G (Gate)
12-22: 0 V counter
(12-22 linked within the base module)
32-42: Input S (Status)
(32-42 linked within the base module)
13-23-33-43: Shield connection
(13-23, 33-43 linked within the base
module)
14: Input A-
24: Input B-
34: Input C-
44: Input L (Latch)
Screw terminals:
PSSu BP-C 2/16S
PSSu BP-C 2/16S-T
Cage clamp terminals:
PSSu BP-C 2/16C
PSSu BP-C 2/16C-T
With C-rail:
11: Input A+
21: Input B+
31: Input C+
41: Input G (Gate)
12-22: 0 V counter
(12-22 linked within the base module)
32-42: Input S (Status)
(32-42 linked within the base module)
13-23-33-43: C-rail supply
Shield connection
(13-23, 33-43 linked within the base
module)
14: Input A-
24: Input B-
34: Input C-
44: Input L (Latch)
21
11
22
12
23
13
24
14
41
31
42
32
43
33
44
34
21
11
22
12
23
13
24
14
41
31
42
32
43
33
44
34