Wiring, General wiring guidelines, 6wiring – Pilz PSSu E S INC User Manual
Page 35: 1 general wiring guidelines

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-1
6.1
General wiring guidelines
6
Wiring
6
6000
Wiring
Wiring
6-
6.1
General wiring guidelines
6100
General wiring guidelines
6-
][Verdrahtung BA Einleitung
Please note:
][Verdrahtung ST INC
The module's connections are galvanically isolated from the module
supply and periphery supply.
For EMC reasons we recommend that you operate inputs A, B, C ex-
clusively as differential inputs with inverted signals (A+/A-, B+/B-, C+/
C-).
The module evaluates open differential inputs (A+/A-, B+/B-, C+/C-)
as a 1 signal.
The module evaluates open function inputs (G, L, S) as a 0 signal.
Use twisted pair cables to carry the inverted signals. This will increase
the noise immunity.
Use shielded signal cables with metallic plugs.
On base modules with C-rail:
– Connect the shield to the terminals on the C-rail.
– Connect the C-rail with low impedance to the functional earth.
On base modules without C-rail:
– Connect the shield as shown in the terminal configuration section.
– The module connects the shield to the functional earth via the
mounting rail.
The channel for the incremental encoder's zero pulse has a different
designation depending on the manufacturer (N, C, Z, 0,...)
The supply voltages must be extra low voltages with safe electrical
separation (PELV or SELV) in accordance with VDE 0100, Part 410.
Use copper wiring.
][Verdrahtung Zusatz mit C
The terminal configuration as stated on the front plate applies for base
modules with C-rail. The terminal configuration as stated in the tech-
nical documentation applies for all other base modules.