1 safety characteristic data, Safety characteristic data – Pilz PSSu E F BSW User Manual
Page 31

Technical Details
Operating Manual PSSu E F BSW(-T)
21372-EN-05
31
Environmental data
312230
314230
Protection type
In accordance with the standard
EN 60529
EN 60529
Mounting (e.g. cabinet)
IP54
IP54
Housing
IP20
IP20
Terminals
IP20
IP20
Mechanical data
312230
314230
Material
Bottom
PC
PC
Front
PC
PC
Coding
PA
PA
Mounting type
plug in
plug in
Dimensions
Height
76,0 mm
76,0 mm
Width
25,2 mm
25,2 mm
Depth
60,2 mm
60,2 mm
Weight
89 g
88 g
Mechanical coding
Type
I
I
Colour
Yellow
Yellow
Safety characteristic data
Operating
mode
EN ISO
13849-1:
2008
PL
EN ISO
13849-1:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2008
T
M
[year]
–
PL e
Cat. 3
SIL CL 3
7,48E-10
SIL 3
1,13E-05
20
If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH
D
and PFD will need to be doubled when a safety function is calculated.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
Information
A safety function's SIL/PL values are
not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.
8.1