Wiring

Operating Manual PSSu E F BSW(-T)
21372-EN-05

25

Connecting the module

21

11

22

12

23

13

24

14

+24 V DC

0 V DC

Periphery Supply

C-rail supply

=

~

N

L1

Connect to the 0 V supply and

earth at a single point

Fuse

PSSu E F BSW/

PSSu E F BSW-T with

- PSSu BS 2/8S(-T)

- PSSu BS 2/8C(-T)

If you are using actuators for safety-related functions, it is essential that you note the follow-
ing:

}

A safety assessment must be made for each individual application.

}

Input modules may not be used within an output block. If an error occurs, input modules

could supply an external voltage which cannot be switched off.

}

The position of each single actuator must be monitored, e.g. via an FS feedback loop

with test pulses.

}

To prevent contact welding, a fuse should be connected before the periphery supply in-

feed (see Technical details).

}

The following applies for floating actuators:

All actuator masses must be fed back to the output modules.

}

The following applies for earthed actuators:

The possibility of a short circuit to + 24 V of the external supply voltage must be exclud-
ed.

When using modules of type PSSu E PD in an output block, please note the following:

}

Do not connect capacitive loads.

}

During the power-up test, the relay contacts are tested with pulses of up to 60 ms.

6.3