2 terminal configuration, Terminal configuration – Pilz PSSu E F BSW User Manual
Page 22

Wiring
Operating Manual PSSu E F BSW(-T)
21372-EN-05
22
Terminal configuration
}
Supply module
– To switch on/off the periphery supply to input/output blocks (block switching)
– To interrupt the incoming (left-hand) periphery supply and C-rail supply
– To provide subsequent (right-hand) modules with the periphery supply and C-rail
supply
Base module
Terminal configuration
Screw terminals:
PSSu BS 2/8S
PSSu BS 2/8S-T
Cage clamp terminals:
PSSu BS 2/8C
PSSu BS 2/8C-T
11: Not assigned
21: Not assigned
12-22: 0 V periphery supply,
interrupted to the left
(12-22 linked within the base
module)
13-23: +24 V periphery sup-
ply,
interrupted to the left
(13-23 linked within the base
module)
14-24: C-rail supply,
interrupted to the left
(14-24 linked within the base
module)
21
11
22
12
23
13
24
14
6.2