Wiring

General wiring guidelines

Please note:

}

Please refer to the technical details regarding the requirements of the supply voltages.

}

Safe electrical isolation must be ensured for the external power supplies that generate

the supply voltages. Failure to do so could result in electric shock.

}

The external power supplies must comply with the current applicable standard

EN 60950-1, EN 61140, EN 50178 or EN 61558-1.

}

The maximum current load for the C-rail is 10 A. Please refer to the derating diagram.

}

Permitted infeed at the C-rail:

– PE
– 0 V
– Shield
– - 30 VDC ... +30 VDC
– - 48 VAC ... + 48 VAC

}

Earth the 0 V supply on the periphery supply or monitor each supply group for earth

faults.

}

The connection of the 0 V supply to the central earth bar or earth fault monitor must be

in accordance with the relevant national regulations (e.g. EN 60204-1, NFPA 79:17-7,
NEC: Article 250).

}

Minimum range for cable cross sections on connection terminals in mm

2

:

– Power supply: 1.5 (AWG16) ... 2.5 (AWG12)
– Functional earth: 1.5 (AWG16) ... 2.5 (AWG12)

}

Use copper wiring.

}

To prevent contact welding, a fuse should be connected before the periphery supply in-

feed (see Technical details).