2 configuration, 1 addressing with safetybus p, 2 addresses in the process image – Pilz PSSu E F BSW User Manual

Page 14: 3 fs error behaviour, Configuration, Addressing with safetybus p, Addresses in the process image, Fs error behaviour

background image

Function description

Operating Manual PSSu E F BSW(-T)
21372-EN-05

14

Configuration

Functions for block switching can be defined in the PSSuniversal Configurator on the
PSS WIN-PRO system software. Block switching is addressed as an FS output in the sys-
tem software:

}

Read access through the standard bus system:

“R” configuration

Information
The PSSuniversal Configurator on the PSS WIN-PRO system software
must be used to define the I/O-Groups to which FS inputs and outputs be-
long (SafetyBUS p). The PSSu can be divided into sections A and B for this
purpose. All the FS outputs on a PSSu always belong to section A.
Section A and section B on a PSSu may belong to different I/O-Groups.

Further information on configuration is available in the PSSuniversal Configurator's online
help.

Addressing with SafetyBUS p

The SafetyBUS p address of an output is composed of the device address and the consec-
utive number of the FS output (.)
The following SafetyBUS p addresses are possible:

SafetyBUS p network

Address range

SafetyBUS p0

O32.00

D

... O95.31

D

SafetyBUS p 1

O132.00

D

... O195.31

D

Addresses in the process image

The module occupies one bit address in the process image. The process image in which
the outputs are shown depends on the configuration of the FS outputs.

Configuration

SafetyBUS p

Standard bus system

FS-PIO

ST-PII

ST-PIO

None

1 Bit

(e.g.: 32.00)

- - -

- - -

Read ST

(“R”)

1 Bit

- - -

FS error behaviour

In the case of a safety-related error on an FS output, all FS outputs in the affected I/O-
Group (SafetyBUS p) are shut down.
In the case of a safety-related error on an FS input, the process image of all FS inputs in
the affected I/O-Group (SafetyBUS p) is set to zero.
The I/O-Group switches to a STOP condition. An error telegram is then triggered on
SafetyBUS p and the error is entered in the PSSuniversal error stack.

4.2

4.2.1

4.2.2

4.2.3