Function description
Operating Manual PSSu E F BSW(-T)
21372-EN-05
12
Function description
Module features
Integrated protection mechanisms
The module has the following protection mechanisms:
}
Periphery supply
– Voltage monitoring (exceeding upper/lower limit)
}
2 relay contacts connected in series to feed the periphery supply: +24 V DC
}
1 relay contact to feed the periphery supply: 0 V DC
}
Thermistor monitor
The module provides the following diagnostic data:
}
Start-up error
}
Configuration error
}
FS communication error
}
Bus termination error
}
Temperatur error: Too warm
}
Temperatur error: Too hot
}
Relay control error
}
Relay error
}
Block switching output error
}
Overvoltage error
}
Undervoltage error
}
Error in the overvoltage protection diodes
Function description
Module supply
}
The module supply provides the module with voltage.
Periphery supply
}
Refreshing the periphery supply: The relevant base module interrupts the connection to
the incoming (left-hand) periphery supply and C-rail on the module bus.
}
Supply to the module bus:
– Periphery supply for subsequent modules (right-hand side)
– C-rail supply for subsequent modules (right-hand side)
}
The module does not automatically switch off the periphery supply in the case of under
or overvoltage. However, there will be a visual signal (LED “24 V”) and a message will
be sent to the head module (entry in the error stack).
Block switch function
}
The module is used to switch off the periphery supply safely on standard modules that
are arranged in blocks.
}
Each output block requires its own block switching module.