beautypg.com

Pilz PSSu E F BSW User Manual

Page 26

background image

Wiring

Operating Manual PSSu E F BSW(-T)
21372-EN-05

26

Connection example

}

Block switching with dual-channel operation and redundant actuator.

}

The ST output module PSSu E S 4DO 0.5 belongs to the output block of the PSSu E F

BSW module.

}

The FS input module for forming the feedback loop (PSSu E F 4DI with test pulses) be-

longs to another supply group, which is not shut down.

}

A maximum of Cat. 3 in accordance with EN 954-1 and SIL2 in accordance with

EN IEC 61508 can be achieved.

Connection example for block switching:

11

12

13

14

21

22

23

24

O0

O1

0 V

0 V

0 V

0 V

K2

K1

11

12

13

14

21

22

23

24

I0

I1

I4

T1

T1

T0

L1

K1

K2

M

K1

K2

PSSu E F 4DI

PSSu E S 4DO 05

K4

K3

L1

K3

K4

M

K3

K4

RFK

K(n)

T0

I3

L1

...

K(n)

M

O2

O3

This manual is related to the following products: