Technical details – Pilz PSSu E F 2DOR 8 User Manual
Page 33

Technical details
Operating Manual PSSu E F 2DOR 8(T)(R)
21334EN07
33
1000
10000
100
10
0,1
1
2
10
5
4
3
6 7 8 9
0,5
DC13: 60 V
DC1: 60 V
D
Nennbetriebstrom (A)
GB Nominal operating current (A)
F
Courant coupé (A)
E
Corriente nominal de servicio (A)
I
Corrente di esercizio nominale (A)
NL Nominale bedrijfsstroom (A)
D
Sc
haltspielzahl x 10
3
GB
Cyc
les x 10
3
F
Nombre de manvres x 10
3
E
Númer
o de cic
los x 10
3
I
Numer
o dei cic
li di comm
utazione x 10
3
NL
Aantal schakelingen x 10
3
Fig.: Service life graph (Rtype)
Example
}
Inductive load: 0,2 A
}
Utilisation category: AC15
}
Contact service life: 1,000,000 cycles
Provided the application requires fewer than 1,000,000 cycles, the PFH value (see tech
nical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contact
ors, use freewheel diodes for spark suppression.
We recommend you use semiconductor outputs to switch 24 VDC loads.