2 terminal configuration, Terminal configuration – Pilz PSSu E F 2DOR 8 User Manual
Page 21

Wiring
Operating Manual PSSu E F 2DOR 8(T)(R)
21334EN07
21
–
Functional earth: 2.5 mm
2
(AWG12)
}
On base modules with screw terminals:
–
If you use a multistrand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C,
although this is not essential. To crimp the ferrules you can use crimp pliers (crimp
form A or C) conforming to EN 609471, such as the PZ 1.5 or PZ 6.5 from
Weidmüller, for example.
–
Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
With Crail
11: Output O0
Relay contact 1
21: Not assigned
1222: Output O0
Relay contact 2
(1222 linked within the base
module)
1323: Crail supply
(13233343 linked within
the base module)
1424: Not assigned
31: Output O1
Relay contact 1
41: Not assigned
3242: Output O1
Relay contact 2
(3242 linked within the base
module)
3444: Not assigned