2 integrated protection mechanisms, 3 reaction times, Integrated protection mechanisms – Pilz PSSu E F 2DOR 8 User Manual
Page 13: Reaction times

Function description
Operating Manual PSSu E F 2DOR 8(T)(R)
21334EN07
13
PSSu E F 2DOR 8 (T)(R): Derating diagram for the permitted ambient temperature T de
pendent on load current I
20
40
60
80
100
0
1
2
3
4
5
6
7
8
9
10
25
T [°C]
I [A]
45
4.1.2
Integrated protection mechanisms
When the PSSu E F PS1(T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.
The module has the following protection mechanisms:
}
1 monitored relay contact per output
}
Protective separation between both relay contacts (see Technical details)
}
Protective separation between both relay contacts and the periphery supply as well as
the module supply, in accordance with DIN VDE 0110 overvoltage category 2 in a pro
tected industrial network
}
Temperature monitoring
The module provides the following diagnostic data:
}
Startup error
}
Configuration error
}
FS communication error
}
Bus termination error
}
Temperature error: Too warm
}
Temperature error: Too hot
}
Relay control error
}
Relay error
4.1.3
Reaction times
Information on the reaction times of the outputs can be found in the PSSuniversal System
Description.