9-2
9.2
Safe monitoring with "reduced speed" operating mode
9200
Safe monitoring with "reduced speed" operating mode
9-
Applikationsbeispiel_DZE_reduzierte Geschwindigkeit-PNOZ ms2p
Safe monitoring with "reduced speed" operating mode
Configuration in the PNOZmulti Configurator
`
Standstill: depending on requirement
`
Speed n1: reduced speed, depending on requirement
`
Speed n2: greater than the maximum permitted speed.
If the "Overspeed" output (see red marking) = "0", either the maximum
permitted speed has been exceeded or the speed monitor has recog-
nised a fault.
"Overspeed" output = "0" must lead to the shutdown of the relevant ax-
is, irrespective of whether the "reduced speed" operating mode is ac-
tive.