beautypg.com

Commissioning, General wiring guidelines, 6commissioning – Pilz PNOZ ms2p TTL coated version User Manual

Page 25: 1 general wiring guidelines

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

6-1

6.1

General wiring guidelines

6

Commissioning

6

6000

Commissioning

Commissioning

6-

6.1

General wiring guidelines

6100

General wiring guidelines

6-

Verdrahtung_multi_Drehzahlwaechter

The wiring is defined in the circuit diagram of the PNOZmulti Configura-

tor.

Details of the input type, axis type and reset mode, plus the values for

standstill, speed monitoring and direction of rotation are also defined in

the PNOZmulti Configurator.

Please note:

`

Information given in the "Technical details" must be followed.

`

Use copper wire that can withstand 75 °C.

Verdrahtung_multi_Drehzahlwaechter_Zusatz_BA

On each of the 2 axes you can connect as required:

`

1 incremental encoder

or

`

2 proximity switches

or

`

1 incremental encoder and 1 proximity switch

CAUTION!

The configurable switch-off delay when reaching the overspeed

increases the reaction time of the system of base unit and speed

monitor by the entered value (see technical details). This must

not impermissibly delay the occurrence of a safe condition. The

configuration of the switch-off delay must be considered in the

risk assessment as regards hazards, reaction time and safety

distance.

Incremental encoders

Proximity switch

Connection axis 1

X12

-

-

I10, I11, 0 V

X12

I10, 0 V

Connection axis 2

X22

-

-

I20, I21, 0 V

X22

I21, 0 V