Commissioning, General wiring guidelines, 6commissioning – Pilz PNOZ ms4p speedcontrol User Manual
Page 21: 1 general wiring guidelines
![background image](https://www.manualsdir.com/files/762662/content/doc021.png)
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-1
6.1
General wiring guidelines
6
Commissioning
6
6000
Commissioning
Commissioning
6-
6.1
General wiring guidelines
6100
General wiring guidelines
6-
The wiring is defined in the circuit diagram of the PNOZmulti Configura-
tor.
Details of the input type, axis type and reset mode, plus the values for
standstill, speed monitoring and direction of rotation are also defined in
the PNOZmulti Configurator.
Please note:
`
Information given in the "Technical details" must be followed.
`
Use copper wire that can withstand 75 °C.
CAUTION!
The configurable switch-off delay when overspeed is reached
increases the reaction time of the system comprising base unit
and speed monitor by the stated value (see technical details).
This must not delay the transfer to a safe condition by more than
the permitted time. The configuration of the switch-off delay
must be considered in the risk assessment as regards hazards,
reaction time and safety distance.