Technical details

Operating Manual PNOZ mm0p-T
1002704-EN-01

25

Mechanical data

772010

Stripping length

9 mm

Dimensions

Height

100,0 mm

Width

45,0 mm

Depth

120,0 mm

Weight

230 g

The standards current on 2012-07 apply.

Safety characteristic data

Unit

Operating

mode

EN ISO

13849-1: 2006
PL

EN ISO

13849-1: 2006
Category

EN IEC 62061
SIL CL

PFH [1/h]

EN ISO

13849-1: 2006
TM [year]

Logic
CPU

PL e

Cat. 4

SIL CL 3

1,54E-09

20

Input
SC inputs

1-channel

PL d

Cat. 2

SIL CL 2

3,95E-09

20

SC inputs

2-channel

PL e

Cat. 4

SIL CL 3

4,61E-10

20

SC inputs

1-ch., pulsed

light beam

device

PL e

Cat. 4

SIL CL 3

3,95E-10

20

Output
SC outputs

1-channel

with ad-

vanced fault

detection

PL e

Cat. 4

SIL CL 3

7,65E-10

20

SC outputs

1-channel

PL d

Cat. 2

SIL CL 2

8,90E-10

20

SC outputs

2-channel

PL e

Cat. 4

SIL CL 3

7,86E-10

20

All the units used with a safety function must be considered wehn calculating the safety
characteristic data.

Information
A safety function´s SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function´s SIL/PL values.