Order reference – Pilz PZE X4V 0,5/24VDC 4n/o fix User Manual
Page 17

PZE X4V
Operating Manual PZE X4V
1003200EN08
17
Service life graphs at 110 V DC
Example
}
Inductive load: 0,2 A
}
Utilisation category: AC15
}
Contact service life: 1,000,000 cycles
Provided the application requires fewer than 1,000,000 cycles, the PFH value (see tech
nical details) can be used in the calculation.
To increase the service life, sufficient spark suppression must be provided on all output
contacts. With capacitive loads, any power surges that occur must be noted. With contact
ors, use freewheel diodes for spark suppression.