Pilz PZE X4V 0,5/24VDC 4n/o fix User Manual
Page 13

PZE X4V
Operating Manual PZE X4V
1003200EN08
13
Electrical data
774586
774583
Max. overall cable resistance Rl
max
Singlechannel at UB DC
30 Ohm
30 Ohm
Voltage at
Input circuit DC
24,0 V
24,0 V
Current at
Input circuit DC
95,0 mA
95,0 mA
Number of output contacts
Safety contacts (N/O), delayed
4
4
Inputs
774586
774583
Number
1
1
Relay outputs
774586
774583
Max. short circuit current IK
1 kA
1 kA
Utilisation category
In accordance with the standard EN 6094741
EN 6094741
Safetycontacts, delayed, AC1
at
240 V
240 V
Min. current
0,01 A
0,01 A
Max. current
6,0 A
6,0 A
Max. power
1500 VA
1500 VA
Safetycontacts, delayed, DC1
at
24 V
24 V
Min. current
0,01 A
0,01 A
Max. current
6,0 A
6,0 A
Max. power
150 W
150 W
Utilisation category
In accordance with the standard EN 6094751
EN 6094751
Safety contacts, delayed AC15
at
230 V
230 V
Max. current
3,0 A
3,0 A
Safety contacts delayed DC13
(6 cycles/min) at
24 V
24 V
Max. current
4,0 A
4,0 A
Utilisation category in accordance
with UL
Voltage
250 V AC G.U. (same polarity)
250 V AC G.U. (same polarity)
With current
6,0 A
6,0 A
Voltage
24 V DC G. U.
24 V DC G. U.
With current
6,0 A
6,0 A
Pilot Duty
B300, R300
B300, R300
Contact fuse protection external,
safety contacts
In accordance with the standard EN 6094751
EN 6094751