Pilz PZE X4V 0,5/24VDC 4n/o fix User Manual
Page 11

PZE X4V
Operating Manual PZE X4V
1003200EN08
11
Conventional thermal
current while loading
several contacts
774580
774581
774582
Ith per contact at UB DC
Conv. therm. current
with 1 contact
6,00 A
6,00 A
6,00 A
Conv. therm. current
with 2 contacts
5,00 A
5,00 A
5,00 A
Conv. therm. current
with 3 contacts
4,50 A
4,50 A
4,50 A
Conv. therm. current
with 4 contacts
4,00 A
4,00 A
4,00 A
Times
774580
774581
774582
Delay time tv
0,50 s
1,00 s
2,00 s
Time accuracy
50 %/+50 %
50 %/+50 %
50 %/+50 %
Supply interruption before
deenergisation
20 ms
20 ms
20 ms
Environmental data
774580
774581
774582
Climatic suitability
EN 60068278
EN 60068278
EN 60068278
Ambient temperature
Temperature range
10 55 °C
10 55 °C
10 55 °C
Storage temperature
Temperature range
40 85 °C
40 85 °C
40 85 °C
EMC
EN 6094751, EN
6100062
EN 6094751, EN
6100062
EN 6094751, EN
6100062
Vibration
In accordance with the
standard
EN 6006826
EN 6006826
EN 6006826
Frequency
10,0 55,0 Hz
10,0 55,0 Hz
10,0 55,0 Hz
Amplitude
0,35 mm
0,35 mm
0,35 mm
Airgap creepage
In accordance with the
standard
EN 609471
EN 609471
EN 609471
Overvoltage category
III / II
III / II
III / II
Pollution degree
2
2
2
Rated insulation voltage
250 V
250 V
250 V
Rated impulse withstand
voltage
4,00 kV
4,00 kV
4,00 kV
Protection type
Mounting area (e.g.
control cabinet)
IP54
IP54
IP54
Housing
IP40
IP40
IP40
Terminals
IP20
IP20
IP20
Mechanical data
774580
774581
774582
Mounting position
Any
Any
Any
Mechanical life
10,000,000 cycles
10,000,000 cycles
10,000,000 cycles