Pilz PZE X4V 0,5/24VDC 4n/o fix User Manual
Page 14

PZE X4V
Operating Manual PZE X4V
1003200EN08
14
Relay outputs
774586
774583
Contact fuse protection external,
delayed safety contacts
Max. melting integral
66 A²s
66 A²s
Blowout fuse, quick
6 A
6 A
Blowout fuse, slow
4 A
4 A
Blowout fuse gG
6 A
6 A
Circuit breaker, 24 V AC/DC,
characteristic B/C
4 A
4 A
Contact material
AgCuNi + 0,2 µm Au
AgCuNi + 0,2 µm Au
Conventional thermal current
while loading several contacts
774586
774583
Ith per contact at UB DC
Conv. therm. current with 1 con
tact
6,00 A
6,00 A
Conv. therm. current with 2 con
tacts
5,00 A
5,00 A
Conv. therm. current with 3 con
tacts
4,50 A
4,50 A
Conv. therm. current with 4 con
tacts
4,00 A
4,00 A
Times
774586
774583
Delay time tv
0,75 s
3,00 s
Time accuracy
50 %/+50 %
50 %/+50 %
Supply interruption before deener
gisation
20 ms
20 ms
Environmental data
774586
774583
Climatic suitability
EN 60068278
EN 60068278
Ambient temperature
Temperature range
10 55 °C
10 55 °C
Storage temperature
Temperature range
40 85 °C
40 85 °C
EMC
EN 6094751, EN 6100062
EN 6094751, EN 6100062
Vibration
In accordance with the standard EN 6006826
EN 6006826
Frequency
10,0 55,0 Hz
10,0 55,0 Hz
Amplitude
0,35 mm
0,35 mm
Airgap creepage
In accordance with the standard EN 609471
EN 609471
Overvoltage category
III / II
III / II
Pollution degree
2
2
Rated insulation voltage
250 V
250 V
Rated impulse withstand voltage
4,00 kV
4,00 kV
Protection type
Mounting area (e.g. control cab
inet)
IP54
IP54
Housing
IP40
IP40
Terminals
IP20
IP20