beautypg.com

Supplementary data, Service life graph – Pilz PZE X4V 0,5/24VDC 4n/o fix User Manual

Page 16

background image

PZE X4V

Operating Manual PZE X4V
1003200­EN­08

16

Supplementary data

CAUTION!

It is essential to consider the relay's service life graphs. The relay outputs'
safety­related characteristic data is only valid if the values in the service life
graphs are met.

The PFH value depends on the switching frequency and the load on the relay output. If the
service life graphs are not accessible, the stated PFH value can be used irrespective of the
switching frequency and the load, as the PFH value already considers the relay's B10d
value as well as the failure rates of the other components.

Service life graph

The service life graphs indicate the number of cycles from which failures due to wear must
be expected. The wear is mainly caused by the electrical load; the mechanical load is negli­
gible.

Service life graphs at 24 V DC and 230 V AC