47

13 Servicing

13346

SILENCER

BRACKET

EARTH

LEAD

IGNITION

LEAD

HEAT

EXCHANGER

13.4 Burner

NOTE:
● The following procedure will require that you replace the

burner door seal and nyloc nuts.
● Removal of the burner is not necessary during a normal

service, but if it is removed it will require a new gasket, see

diagram 13.6.
● When replacing ensure that the sealing grommet, situated
below the gas valve is correctly re-seated.
Slacken the gas connection at the union nut between the

boiler module and tank module.
Remove the gas supply pipe securing clip and withdraw the

gas pipe from gas valve, see diagram 13.10.
Disconnect the electrical connection at the gas valve and

disconnect the electrical connection from the fan, see diagram

13.10.
Disconnect the ignition lead and earth lead from the burner

door, see diagram 13.9.
Disconnect the flue overheat thermostat, see diagram 13.11.
Remove the four burner door nyloc nuts, one of these also

holds the silencer bracket, see diagram 13.11.

Gently remove the fan, gas valve and burner assembly from

the combustion chamber, taking care not to trap the primary

return thermistor electrical cables.

Clean the burner with a soft brush taking great care not to

damage the front insulation. DO NOT use wire or sharp

instruments to clean the holes of the burner. Inspect the

burner for any signs of damage.

Remove and discard the burner door seal and replace with

new.

13.5 Heat Exchanger

Refer to diagram 13.11.
Remove loose debris from inside the heat exchanger using a

soft brush and vacuum cleaner.
Carefully flush by spraying water into the heat exchanger, any

remaining debris should pass through the condensate trap

(Ensure the water is kept away from electrical components).

ELECTRICAL

CONNECTION

GAS VALVE

FAN

ELECTRICAL

CONNECTION

GAS SUPPLY PIPE

SECURING CLIP

Diagram 13.10

13350

13373

NYLOC

NUT (4 OFF)

GAS VALVE

FAN

BURNER

DOOR

SILENCER

BRACKET

SEAL

HEAT EXCHANGER

FLUE

OVERHEAT THERMOSTAT

Diagram 13.11

Diagram 13.9