9.2 Condensate Drain Connection
A flexible condensate hose runs from a push-fit connection at
the bottom of the heat exchanger and terminates on the boiler
module base plate, see diagram 8.2.
Connect the flexible condensate hose to the boiler module,
see diagram 9.2.
A flexible condensate connection pipe is supplied in the loose
items pack and should be fitted between the condense trap
and siphonic drain to the condensate drain pipe, see diagram
9.3, and refer to section 6 to discharge condensate to a drain.
The drain pipe 22mm to 25mm OD. non corrosive plastic pipe
should have a fall of at least 2.5
0
away from the boiler.
CONDENSE TRAP
& SIPHONIC DRAIN
FLEXIBLE
CONDENSATE
HOSE
FLEXIBLE
CONDENSATE
CONNECTION
PIPE
13312
Diagram 9.2
Diagram 9.3
13458
FLEXIBLE
CONDENSATE
HOSE
FLEXIBLE CONDENSATE
HOSE CONNECTION TO
BOILER MODULE
9 Condensate & Safety Discharge Valve Connections
9.1 Safety Discharge Valve
The pipes must be extended, using not less than 22mm o.d.
pipe, to discharge, in a visible position, outside the building,
facing downwards, preferably over a drain.
The pipe must have a continuous fall and be routed to a
position so that any discharge of water, possibly boiling,
or steam cannot create any danger to persons, damage to
property or external electrical components and wiring.
It is advisable to use a 22mm compression elbow to aid in
future servicing, see diagram 9.1.
13463
CH SAFETY RELIEF VALVE
DISCHARGE CONNECTION
DHW SAFETY RELIEF VALVE
DISCHARGE CONNECTION
22mm compression
(not supplied)
is the preferred method of
connection for servicing.
Diagram 9.1