10.7 Standard Horizontal Flue
Refer to diagram 10.12 for kit contents.
10.8 REAR Flue
With the flue elbow temporarily fitted, measure the distance
from the outside wall to the butt joint, see diagram
10.14.
If
the measurement ‘Y’ exceeds 667mm, then the appropriate
length of extension pipe is required. The minimum dimension
is 156mm to suit a 75mm min wall thickness. The flue can
project to a maximum of 600mm, if this is desirable, refer to
diagram 10.16.
10.9 SIDE Flue
With the flue elbow temporarily fitted, measure the distance
from the outside wall to the butt joint, see diagram
10.15.
If
the measurement ‘Y’ exceeds 667mm, then the appropriate
length of extension pipe is required. The minimum dimension
for LH is 408mm and RH 195mm to suit a minimum wall
thickness of 75mm. The flue can project to a maximum of
600mm, if this is desirable, refer to diagram 10.16.
10.10 Flue Fitting
IMPORTANT:-
The flue seals are sensitive to mineral oil based lubricants.
Do
not grease the seals. If the seals do need to be lubricated
use only water.
During the installation of the flue system, ensure that debris
such as mortar, filings or swarf are cleared from the flue
system before completion.
Long lengths of flues must be secured to the walls or ceilings
they run against. Use at least one fixing bracket for every flue
extension that is used.
After cutting inner flue tubes ensure that you de-burr and
chamfer the male tube end to prevent damage.
Inspect the flue pipes before fitting and do not install damaged
or dented flue components.
When assembling the flue system, ensure that the inner
seals are not damaged, do not install a flue component with a
damaged seal.
When fitting flue elbows ensure that they are fitted at the
correct angle to avoid strain, this will ensure that the seal fits
correctly preventing leakage.
Remove the flue elbow.
Separate the flue duct from the terminal by twisting to release
the terminal catch, then pull out of the retaining seal, refer to
diagram 10.17.
The flue duct cutting length (L + 11mm.) is shown in diagram
10.17.
The air duct should be cut at the opposite end to the terminal
The plastic flue duct MUST be cut at the opposite end to the
terminal catch.
The plastic flue duct extensions MUST be cut at the opposite
end to seal.
Insert the flue duct into the air duct terminal assembly,
remembering to engage the catch within the terminal.
Fit the sealing collar onto the locating ring on the flue terminal,
see diagram 10.8.
13224
Left Hand illustrated
10 Standard Flue - Length, Preparation and Installation
Diagram 10.14
13223
12979
Diagram 10.15
Diagram 10.16