3 flue options and terminal clearances – Glow-worm Ultrapower sxi Range User Manual
Page 11
11
HORIZONTAL FLUES
A DIRECTLY BELOW AN OPENING, AIR BRICK,
OPENING WINDOWS
300
B
ABOVE AN OPENING, AIR BRICK,
OPENING WINDOWS
300
C
HORIZONTALLY TO AN OPENING,
AIR BRICK, OPENING WINDOWS
300
D BELOW GUTTER, DRAIN/SOIL PIPE
25
E BELOW EAVES
25
F BELOW A BALCONY OR CAR PORT
25
G FROM VERTICAL DRAIN PIPES AND
SOIL PIPES
25
H FROM INTERNAL/EXTERNAL CORNERS
25
H
*
TO A BOUNDARY ALONGSIDE THE
TERMINAL
300
I
ABOVE ADJACENT GROUND OR
BALCONY LEVEL
300
J
*
FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL
600
K FACING TERMINALS
1200
L FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING
1200
M VERTICAL FROM A TERMINAL
1500
N HORIZONTALLY FROM A TERMINAL
300
VERTICAL FLUES
P
FROM ANOTHER TERMINAL
600
Q ABOVE ROOF LEVEL
300
R
FROM ADJACENT OPENING WINDOW
1000
S
FROM ADJACENT WALL TO FLUE
300
Diagram 3.1
3.1 Flue Options
There are various flue options to choose from as illustrated in
diagram 3.3. The flue lengths and installation of various flue
types are described in section 10.
3 Flue Options and Terminal Clearances
Diagram 3.2
15583
3.2 Flue Terminal Position
The minimum acceptable siting dimensions for the terminal
from obstructions, other terminals and ventilation openings
are shown in diagram 4.2. In IE the minimum distances for
flue terminal positioning must be those detailed in I.S.813
“Domestic Gas Installations”.
The terminal must be exposed to the external air, allowing free
passage of air across it at all times.
Being a condensing boiler some pluming may occur from
the flue outlet. This should be taken into consideration when
selecting the position for the terminal.
NOTE: If necessary it is permitted to increase the terminal
protrusion through the outside wall to greater than the
minimum dimension of 87mm but no more than 600mm.
Carports or similar extensions of a roof only, or a roof and
one wall, require special consideration with respect to any
openings, doors, vents or windows under the roof. Care is
required to protect the roof if made of plastic sheeting. If
the carport comprises of a roof and two or more walls, seek
advice from the local gas supply company before installing the
boiler.
H* and J* See diagram 4.2 . These dimensions comply with
the building regulations, but they may need to be increased to
avoid wall staining and nuisance from pluming depending on
site conditions.
NOTE: If the flue terminal is positioned near a light source
insects may enter the flue system. Where safe and practical to
do so advise the homeowner to check the flue outlet and clear
visible insects from the terminal end.
Plume Management Kit: Part No.A2044100 (white) or
A2044000 (black) can be used to overcome many site issues.
3.3 Terminal Guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
minimum of 50mm clearance from any part of the terminal and
be central over the terminal.
The guard should be similar to that shown in diagram 3.2.
A suitable guard is manufactured by: -
Tower Flue Components
Morley Rd.
Tonbridge
Kent TN9 1RA.
Size: 280mm x 165mm. Part No. CGDK3