10 plume management kit, 11 electrical connection – Glow-worm Ultrapower sxi Range User Manual
Page 37
37
10 Plume Management Kit
10.13 Plume Management Kit
The Plume Management Kit: Part No. A2044100 (white) or
A2044000 (black) can be used to overcome many site issues.
The Plume Management Kit will fit to the Top Horizontal
Telescopic, Rear Horizontal Telescopic and Standard
Horizontal Flue. This enables the flue products to exhaust
further away from the boiler, thereby reducing the impact
of pluming. The flue air inlet can be sited closer to doors,
opening windows and air bricks, see diagram 10.30.
The maximum length of the Plume Management Kit must NOT
exceed 6m with a horizontal concentric flue length of 2m max.
For each 90
o
bend or 2 x 45
o
bends the maximum length of the
Plume Management Kit must be reduced by 1m.
For more information contact Glow-worm, refer to page 2.
The Plume Management Kit is supplied with installation
instructions.
Refer to BS5546 or BS6798 for advice on disposal of boiler
condensate.
Diagram 10.30
12997
WARNING: This appliance must be earthed.
● This appliance must be wired in accordance with these
instructions. Any fault arising from incorrect wiring cannot be
put right under the terms of the Glow-worm guarantee.
● All system components must be of an approved type.
Electrical components have been tested to meet the
equivalent requirements of the BEAB.
● Do not interrupt the mains supply with a time switch or
programmer.
● Connection of the whole electrical system and any heating
system controls to the electrical supply must be through a
common isolator.
● Isolation should preferably be by a double pole switched
fused spur box having a minimum contact separation of
3mm on each pole. The fused spur box should be readily
accessible and preferably adjacent to the boiler. It should be
identified as to its use.
● A fused three pin plug and shuttered socket outlet may be
used instead of a fused spur box provided that:
a) They are not used in a room containing a fixed bath or
shower.
b) Both the plug and socket comply with the current issue of
BS1363.
11 Electrical Connection
Immersion Heater
- the thermostatically controlled
immersion heater with manual reset is fitted to the cylinder
as a back up for domestic hot water in the event of the boiler
being inoperable, it MUST be wired separately from the boiler
electrical connections.
The heater should be wired through a double-pole switch or
controller having a minimum contact separation of 3mm on
each pole. Use a cable size of at least 1.5sq. mm flexible
cable, 85 deg.C rubber insulated HOFR sheathed to comply
with BS6141 Table 8 and must be fully earthed.