beautypg.com

12 commissioning – Glow-worm Ultrapower sxi Range User Manual

Page 42

background image

42

12 Commissioning

12.7 Range Rating

The boilers are fully modulating for central heating, and it is

therefore not necessary to range rate the boiler. However, if

desired, it is possible to range rate the boiler between 9 and

24kW in 1kW increments, refer to diagram 12.4, then:

a) Press and hold the ‘MODE’ button for 5 seconds.

The display will change to flashing ‘0’.

b) Use the ‘+’ or ‘-’ button to scroll to 96.

c) Press ‘MODE’ to confirm.

d) The display now shows a flashing ‘d. 0’. The part

load setting is displayed above in kW

e) Press ‘MODE’ to change, use the ‘+’ or ‘-’ button

to change this value to the desired setting.

h) Press ‘MODE’ to confirm, the new setting has been

saved.

i) Press and hold ‘MODE’ to exit.

NOTE: For approximate gas rates at part load, refer to table

opposite.

12.8 Water Systems

Check that all external controls are calling for heat, the boiler

will fire automatically. Fully open all radiator valves and the

flow control valve, if fitted, see diagram 4.1.
Balance the radiators as required and if fitted adjust the valve

to give the required system differential. Turn off all radiators

that can be shut off by the user and check to see if less than

the maximum differential allowed of 20

o

C can be achieved

across flow and return.
The pump has two speeds and can be adjusted depending on

the requirements of the central heating system, see diagram

4.2.
The boiler has an inbuilt automatic adjustable bypass valve.

The pressure can be adjusted between approx 1.5 and

3.5mH

2

O but is factory pre-set to approx 2.5mH

2

O. The

pressure changes by approx 0.1mH

2

O for each full turn

of the bypass screw, see diagram 12.5. Turning clockwise

increases the pressure and turning anti-clockwise decreases

the pressure.
Allow the system to reach maximum temperature then switch

off the boiler by isolating from the electrical supply.
Lock or remove the handle from the control valve, if fitted.

Adjust the boiler temperature controls and any system

controls to their required settings.
We recommend that the domestic hot water should be run for

a short period until clear.

12.5 Re-pressurising System (if required)

1. Ensure that the filling loop flexible hose is securely

connected to the double check inlet valve, see diagram

12.3.
2. Fully open tap”A”, then gradually open tap “B” to fill the

heating system to a pressure of 1.0bar. When completed

close the filling taps.
3. Vent all air from the system - repeat step 2 as necessary

until the system is full and all the air has been removed.
4.

IMPORTANT: To comply with the water regulations the

flexible hose must be disconnected from the double check

inlet valve - undo the nut and pull the flexible hose from

the valve.

12.6 Gas Inlet Pressure and Gas Rate

The supply from the governed meter must be of adequate size

to provide a steady inlet working pressure of 20mbar (8in wg) at

the boiler. On completion, test the gas installation for tightness

using the pressure drop method and suitable leak detection

fluid, purge as necessary.
NOTE: Due to the modulating operation of the boiler and the

need to check the gas inlet pressure and measure the gas rate

at maximum rate, it will be necessary to force it to maximum.
Press the “reset” button on the controls fascia, release

and immediately press and hold in the “+” button. After

approximately 5 seconds “Hi” will be displayed. Pressing

the mode button when “Hi” is selected will force the boiler

to maximum rate, the display will flash between “Hi” and the

“default display” this will indicate the boiler has been forced to

maximum.

Operational Gas Inlet Pressure

With ALL other gas appliances operating, check the operational

supply pressure at the gas service isolation valve test point, see

diagram 12.1.

The nominal supply pressure for Natural Gas (G20) is 20mbar.

The nominal supply pressure for LPG (G31) is 37mbar.

Turn the taps and appliances off, then disconnect the pressure

gauge.

NOTE:

If you require to measure the gas inlet pressure at the

gas valve there will be a pressure drop over the gas service

isolation valve, this is normal and the inlet pressure can be up

to 2mbar less.

Additionally the safe nominal maximum heat input of the

appliance can be achieved at an inlet pressure down to 15mbar.

NOTE:

The

BURNER PRESSURE cannot be measured.

Gas Rate

Make sure that ALL other gas burning appliances and pilot

lights are off.

Check the gas rate using the gas meter test dial and stop

watch, at least 10 minutes after the burner has lit, see table

opposite for approximate rates.

In communal or LPG installations where the gas rate cannot be

measured it is acceptable to measure the combustion rate as

described in the servicing section.

On completion, press the “mode” and “+” buttons

simultaneously, this will reset the boiler.

kW

m3/hr ft3/hr

kW

m3/hr ft3/hr

24

2.5

88.6

16

1.7

58.9

23

2.4

84.7

15

1.6

55.4

22

2.3

81.2

14

1.5

51.5

21

2.2

77.3

13

1.4

48.0

20

2.1

73.8

12

1.3

44.1

19

1.1

69.9

11

1.2

40.6

18

1.9

66.4

10

1.0

36.7

17 1.8

62.9

9

0.9

33.2