beautypg.com

5 domestic hot water – Glow-worm Ultrapower sxi Range User Manual

Page 15

background image

15

5 Domestic Hot Water

5.5 SYSTEM REQUIREMENTS – Domestic Hot

Water

Domestic Hot Water Requirements

NOTE: Attention is drawn to the following extracts from the

Building Regulations 1991.

Regulation 11(1) (Giving of a building notice or deposit of

plans)

“Subject to the following provisions of this regulation, a person

who intends to carry out building work or to make a material

change of use shall:

a) Give to the local authority* a building notice in accordance

with 12; or

b) Deposit full plans with the local authority* In accordance

with regulation 13”.

Regulation 12(4) (Particulars and plans where a building

notice is given)

“………a building notice shall be accompanied by a statement

which specifies:

*Attention is drawn to regulation 18 (supervision of building

work otherwise than by local authorities).

a) The name, make, model and type of hot water storage

system to be installed;

b) The name of the body, if any, which has approved or

certified that the system is capable of performing in a

way which satisfies the requirements of paragraph G3 of

Schedule 1;

c) The name of the body, if any, which has issued any

current registered operative identity card to the installer or

proposed installer of system.”

Regulation 13(3) (Full plans)

“Full plans shall consist of:

a) Description of the proposed building work or material

change of use, and the plans, particulars and statements

required by paragraphs (1) to (4) of regulation 12: and

…….”

NOTE:

Bye-laws of the appropriate Water Undertake also apply.

Discharge Pipework

It is a requirement of Building Regulation G3 that any

discharge from an unvented system is conveyed to where it

is visible but will not cause danger to persons in or about the

building. The tundish and discharge pipes should be fitted in

accordance with requirements and guidance notes of Building

Regulation G3. The G3 Requirements and Guidance section

3.9 are reproduced in the following sections. Information

Sheet No. 33 available from the British Board of agreement

gives further advice on discharge pipe installation. For

discharge pipe arrangements not covered by G3 Guidance or

BBA info sheet no. 33 advice should be sought from your local

Building Control Officer.

G3 Requirement

“….there shall be precautions….. to ensure that the hot water

discharged from safety devices is safely conveyed to where it

is visible but will not cause danger to persons in or about the

building”.

G3 Guidance SECTION 3.9

The discharge pipe (D1)from the vessel up to and including

the tundish is generally supplied by the manufacturer of the

hot water storage system. Where otherwise, the installation

should include the discharge pipe(s) (D1) from the safety

device(s). In either case the tundish should be vertical,

located in the same space as the unvented hot water storage

system and be fitted as close as possible and within 500mm

of the safety device e.g. the temperature relief valve.

NOTE: The tundishes are factory fitted during manufacture.

The discharge pipe (D2) from the tundish should terminate in

a safe place where there is no risk to persons in the vicinity of

the discharge, preferably be of metal and:

a) Be at least one pipe size larger than the nominal outlet

size of the safety device unless its total equivalent hydraulic

resistance exceeds that of straight pipe 9m long i.e. discharge

pipes between 9m and 18m equivalent resistance length

should be at least two sizes larger than the nominal outlet

size of the safety device, between 18 and 27m at least 3

sizes larger and so on. Bends must be taken into account in

calculating the flow resistance.

An alternative approach for sizing discharger pipes would be

to follow BS67100:1987 specification for design installation,

testing and maintenance of services supplying water for

domestic use within buildings and their curtilages. Appendix E

section E2 and table 21.

b) Have a vertical section of at least 300mm long, below the

tundish before any elbows or bends in the pipework.

c) Be installed with a continuous fall.

d) Have discharges visible at both the tundish and the

final point of discharge but where this is not possible or is

practically difficult there should be clear visibility at one or

other of these locations. Examples of acceptable discharge

arrangements are:

i) Ideally below a fixed grating and above the water seal in a

trapped gully.

ii) Downward discharges at low level; i.e. up to 100mm above

external surfaces such as car parks, hard standings, grassed

areas etc. are acceptable providing that where children may

play or otherwise come into contact with discharges a wire

cage or similar guard is positioned to prevent contact whilst

maintaining visibility.

iiI) Discharges at high level; e.g. into a metal hopper and

metal down pipe with the end of the discharge pipe clearly

visible (tundish visible or not) or onto a roof capable of

withstanding high temperature discharges of water and 3m

from any plastic guttering system that would collect such

discharges (tundish visible).

iv) Where a single pipe serves a number of discharges,

such as in blocks of flats, the number served should be

limited to not more than 6 systems so that any installation

discharging can be traced reasonably easily. The single

common discharge pipe should be at least one pipe size

larger than the largest individual discharge pipe (D2) to

be connected. If unvented hot water storage systems are

installed where discharges from safety devices may not be

apparent i.e. in dwellings occupied by blind, infirm or disabled

people, consideration should be given to the installation of an

electronically operated device to warn when discharge takes

place.