beautypg.com

A caution – Carrier 38E User Manual

Page 9

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

every 30, 50 or 90 minutes of operating time. Control
board has additional feature that allows unit to restart in
defrost cycle if room thermostat is satisfied during
defrost.

Troubleshooting defrost control involves a series of

simple steps that indicate whether board is defective.

NOTE: Procedure allows mechanic to check control
board and defrost thermostat for defects. First, trouble­
shoot to make sure unit operates properly in heating and
cooling modes. This ensures problems are not attributed

to the defrost control board. Additional steps follow:

1. Turn thermostat to OFF. Disconnect all power to

outdoor unit.

2. Remove control box cover for access to electrical

components and defrost control board.

3. Disconnect defrost thermostat leads from control

board, connect to ohmmeter. Thermostat leads are

the heavy-gage black insulated wires connected to

DFT and C terminals on control board. Resistance
reading may be 0 (indicating closed defrost thermo­

stat) or infinity ( oo for open thermostat) depending
on outdoor temperature.

4. Jumper between DFT and C terminals on control

board as shown in Fig. 9.

5. Disconnect outdoor fan motor lead. Tape lead to

prevent grounding.

6. Restart unit in heating, allowing frost to accumulate

on outdoor coil.

7. After a few minutes in heating, liquid line tempera­

ture should drop below closing set point of defrost
thermostat. Using ohmmeter, check resistance across
defrost thermostat leads. Resistance of 0 indicates

defrost thermostat is closed and operating properly.

8. Remove protective cover from TPl and TP2 speed­

up terminals. Insert jumper wire into protective
cover, reinsert protective cover on speed-up termi­
nals. This reduces by 1 / 4 timing sequence of original
time (see Fig. 10). Since Fig. 10 shows timing cycle set

at 30 minutes, unit initiates defrost within approxi­
mately 30 seconds; if setting is at 50 minutes, within

Fig. 10 — Inserting Jumper Wire

into Protective Cover

50 seconds; 90 minutes, within 90 seconds. When you
hear reversing valve change position, remove protec­

tive cover/jumper, otherwise control will terminate

normal 10-minute defrost cycle in approximately

10 seconds.

A CAUTION

Do not use screwdriver or other means to short
speed-up pins. If pins are accidentally grounded,
control board is destroyed.

9. Unit is now operating in defrost mode. Using volt­

meter, check between R and W2 as shown in Fig. 11.

Fig. 11 — Checking Between R and W2