beautypg.com

Carrier AQUAZONE 50QE900-250FS User Manual

Owner’s manual

background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 535-00111

Printed in U.S.A.

Form 50QE-4SO

Pg 1

6-03

Replaces: New

Book 1

4

Tab

5a

5a

Owner’s Manual

Part Number 50QE900-250FS

CONTENTS

Page

GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Thermostat Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Heat or Cool Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Thermostat Front Panel Buttons . . . . . . . . . . . . . . . . . 1
Keypad Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Set Clock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Program Thermostat Schedules. . . . . . . . . . . . . . . . . . 2
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Auto-Changeover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Two-Stage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Clock Backup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Emergency Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Holiday Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dry Contact Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Remote Temperature Sensor . . . . . . . . . . . . . . . . . . . . . 4

GENERAL

Carrier’s Aquazone 7-day, commercial, programmable ther-

mostats are flat, wall-mounted, low-voltage thermostats which
maintain room temperature by controlling the operation of an
HVAC (heating, cooling and ventilation) system. Separate
heating and cooling set points and auto-changeover capability
allow occupied and unoccupied programming schedules for
energy savings.

All thermostats allow up to 3 occupied and one unoccupied

time/temperature settings to be programmed per 24-hour peri-
od. Each thermostat stores programs for 7 independent days.
Batteries are not required. During power interruption the inter-
nal NEVERLOST™ memory stores programmed schedules
for an unlimited time.

CONFIGURATION

Thermostat Display —

The thermostat display is locat-

ed in the center of the thermostat. See Fig. 1. The following
information can be displayed on the screen:

mode (OFF, HEAT, COOL, AUTO, or PROGRAM ON)

fan setting (FAN ON or blank)

override indication

room temperature

desired temperature

service filter indicator

time of day

day of the week

schedule period (Occupied 1, 2, or 3; or Unoccupied)

setup indicator (Programming mode)

lock indicator

start/stop indicator (schedule period Programming mode)

Heat or Cool Indicator —

A Heat or Cool indicator is

located in the middle of the thermostat. See Fig. 2. The light
will be red if the thermostat is in Heating mode. The light will
be green if the thermostat is in Cooling mode.

Thermostat Front Panel Buttons —

The thermostat

has buttons on the front cover which are used to raise or lower
the desired set point, change the mode, program, and override
the current program. See Fig. 2.
SET POINT BUTTONS — The UP ARROW and DOWN
ARROW buttons will raise or lower the current desired tem-
perature set point. If the thermostat is in AUTO mode, pressing
the UP ARROW or DOWN ARROW buttons will adjust both
the heating and cooling set points. Pressing the UP ARROW or
DOWN ARROW buttons in Cooling mode will adjust only the

IMPORTANT: Read entire instructions before program-
ming the thermostat.

IMPORTANT: The thermostat has a configurable secu-
rity level. If certain functions are not available (changing
set points, changing programming schedules), the ther-
mostat security level may be configured to exclude those
functions. Call the installer to reconfigure the security
level.

Fig. 1 — Thermostat Display

50QE900

Aquazone™ Water Source Heat Pump

Flush-Mounted Flatstat

Commercial Programmable Thermostat