beautypg.com

2 venting – Reznor X Unit Installation Manual User Manual

Page 9

background image

Form I-X, P/N 150491 R10, Page 9

6.1.2 Manifold or

Orifice Pressure

Settings

Measuring manifold gas pressure cannot be done until the heater is in operation. It is

included in the steps of the "Check-Test-Start" procedure in Paragraph 9.0. The follow-

ing warnings and instructions apply.

WARNING

Manifold gas pressure must never exceed 3.5" w.c. for natural gas and

10" w.c. for propane gas.

For Natural Gas: When the heater leaves the factory, the combination valve is set so

that the outlet gas pressure of a single-stage valve or high fire of a two-stage valve

is regulated to 3.5" w.c. Low fire on a two-stage valve is set to 1.8" w.c. Inlet supply

pressure to the valve must be a minimum of 5" w.c. or

as noted on the rating plate

and a maximum of 14" w.c.

NOTE: Always check the rating plate for minimum gas

supply pressure. Minimum supply pressure requirements vary based on the size of

the burner and the gas control option. Most units require a minimum of 5" w.c. of natu-

ral gas as stated above, but Sizes 350 and 400 with electronic modulation require a

minimum of 6" w.c. natural gas supply pressure. Sizes 300 and 350 with mechanical

modulation require 7" w.c.
For Propane: When the heater leaves the factory, the combination valve is set so that

the outlet gas pressure of a single-stage valve or high fire of a two-stage valve is 10"

w.c. Low fire on a two-stage valve is set to 5" w.c. Inlet pressure to the valve must be

a minimum of 11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust manifold gas pressure, the inlet (supply) pres-

sure must be within the specified range for the gas being used both when the heater is

in operation and on standby. Incorrect inlet pressure could cause excessive manifold

gas pressure immediately or at some future time.
Instructions to Check Manifold Pressure

:

1) With the manual valve (on the combination valve) positioned to prevent flow to the

main burners, connect a manometer to the 1/8" pipe outlet pressure tap in the valve.

NOTE: A manometer (fluid-filled gauge) is recommended rather than a spring type

gauge due to the difficulty of maintaining calibration of a spring type gauge.

2) Open the valve and operate the heater. Measure the gas pressure to the manifold. To

measure the low stage pressure on units equipped with a two-stage valve, disconnect

the wire from the "HI" terminal on the valve. (Be sure to reconnect wire.)

Normally adjustments should not be necessary to the factory preset regulator. If adjust-

ment is necessary, set pressure to correct settings by turning the regulator screw IN

(clockwise) to increase pressure. Turn regulator screw OUT (counterclockwise) to

decrease pressure.

CAUTION: DO NOT

bottom out the gas

valve regulator

adjusting screw.

This can result

in unregulated

manifold pressure

causing excess

overfire and heat

exchanger failure.

6.2 Venting

DANGER

Failure to provide proper venting could result in death, serious injury, and/or property

damage. This furnace must be installed with a vent connection and proper vent to the

outside of the building. Install vent in accordance with Part 7, Venting of Equipment,

of the National Fuel Gas Code, ANSI Z223.1 (latest edition) or applicable provision of

national, state or local codes. A Canadian installation must be in accordance with the

CSA B149.1 and B149.2, Installation Code for Gas Burning Appliances and Equipment,

and applicable local codes. Also, comply with venting requirements in this Paragraph.

Safe operation of any gravity-vented gas-fired equipment requires a properly operating

vent system, correct provision for the combustion air (See Paragraph 2.2) and regular

maintenance and inspection. See Hazard Levels, page 2.

6.2.1 Venting

Requirements

1. Provide a minimum clearance of 18" between the drafthood relief opening and any

obstruction. Do not expose the relief opening to wind drafts from any source such

as from an overhead door or adjacent air handling equipment.

Consult the valve manufacturer's literature provided for more detailed information.