beautypg.com

6 burner carryover system and air adjustment, 0 controls (cont'd), 5 pilot and ignition systems (cont'd) – Reznor X Unit Installation Manual User Manual

Page 22

background image

Form I-X, P/N 150491 R10, Page 22

CAUTION: Due to high voltage on pilot spark wire and pilot electrode, do

not touch when energized. See Hazard Levels, page 2.

If no spark occurs, check the following:

a) Voltage between Terminals TH and 7 should be at least 20 volts and no higher

than 32 volts. Refer to Troubleshooting (Paragraph 10.3) if no voltage is observed.

b) Short to ground in the high tension lead and/or ceramic insulator.

c) Pilot spark gap should be approximately 7/64".

NOTE: When checking

for spark with the pilot

burner assembly removed

from the burner rack, the

pilot assembly must be

grounded to the heater for

proper spark.

FIGURE 23 - Spark Pilot

-- Maintain a spark gap

of 7/64"

Flame Sensing Probe

Pilot

Orifice

Centerline of

first burner

High Tension

Lead

Burner

Rack

Front

Spark Electrode

Spark Gap

7/64” (2.78mm)

TOP VIEW OF BURNER

TOP VIEW

SIDE

VIEW OF

PILOT

1/4”± 1/32”

(6.38mm±.79)

23/32”

(18.25mm)

7/16”± 1/16”(11mm±1.6)

If the above conditions are normal and no spark occurs, replace the ignition controller.
If the main gas valve fails to open with a normal full size pilot flame established, check

for the following:

a) Voltage between black and brown leads on the main gas valve is 20 to 32 VAC

and there is no main gas flow with the built-in manual valve in FULL OPEN

position -- the main valve is defective.

b) No voltage between black and brown leads on the main gas valve -- check for

disconnected or shorted flame sensor lead or flame sensor probe.

When the above conditions are normal and the main gas flow is still off, the ignition

controller is probably defective.
NOTE: Model X furnaces manufactured prior to 10/2003 may be equipped with a

match-lit pilot.

8.6.1 Burner Carryover

These duct furnaces have individually formed steel burners with accurately die-formed

ports to give controlled flame stability without lifting or flashback with either natural or

propane gas. The burners are lightweight and factory mounted in an assembly which

permits them to be removed as a unit for inspection or service.
All natural gas burners are equipped with two flash carryover systems that receive

a supply of gas simultaneously with the main burner. All propane gas burners are

equipped with one flash carryover and a regulated gas lighter tube system. During

regular service, check the main burner ports, the carryover assemblies, and the ori-

fices for cleanliness.

8.6.2 Burner Air

Adjustment

8.6 Burner

Carryover

System and Air

Adjustment

8.0 Controls

(cont'd)

Burner air shutters are not normally required on natural gas furnaces. Air shutters are

required on propane gas units and may require adjustment.
Before making any adjustments to the air shutters, allow the heater to operate for

about fifteen minutes with the air shutters open. The slotted screw on the end manifold

bracket moves the air shutters and adjusts all burners simultaneously. Turning the

screw clockwise opens the shutters; counterclockwise closes the shutters. After the

furnace has been in operation for 15 minutes, close the air shutters observing the flame

for yellow-tipping. Open the shutters until the yellow disappears. A limited amount of

yellow-tipping is permissible for liquefied petroleum gases. Natural gas should not dis-

play any yellow-tipping.

8.5 Pilot and

Ignition

Systems

(cont'd)