Form I-X, P/N 150491 R10, Page 18

FIGURE 17 - Wiring Diagram for Model X Furnace with Spark Pilot and Two-Stage Gas Valve

6

7

8

9

10

11

12

13

14

15

16

17

18

FACTORY WIRING

FIELD WIRING

WHITE - W

PURPLE - PR

BLUE - BL

GREEN - G

YELLOW - Y

ORANGE - O

RED - R

BROWN - BR

BLACK - BK

WIRING CODE

TOTAL WIRE MINIMUM RECOMMENDED
LENGTH WIRE SIZE
150 FEET #18 GA.
250 FEET #16 GA.
350 FEET #14 GA.

FIELD CONTROL WIRING

BLOWER RELAY

CUST. 24 VOLT

COIL

CR

16

DISCONNECT SWITCH

LINE/1/60

G

GRD

BL

R

Y

LIMIT

CONTROL

26

25

24

23

22

21

20

19

OPT. FACTORY WIRING

BK

BR

19

H

TD

H

BR

BR

BK

BL

16

FAN TD
HEATER

LOW
STAGE

PILOT

BLOCKED VENT

SWITCH

MANUAL RESET

Y

27

40 VA. CONTROL

BK

BL

24V

LINE VOLT

BR

R

TRANSFORMER

Y

R

R

HIGH
STAGE

13

12

4

11

7

7

7

7

10

8

B

W

- SET THERMOSTAT SWITCH AT "OFF" POSITION.
- TURN ON POWER, MAIN AND PILOT MANUAL GAS VALVES.
- SET THERMOSTAT SWITCH AT "AUTO" POSITION.

- LOW STAGE OF THERMOSTAT CALLS FOR HEAT.

- ENERGIZING THE IGNITION CONTROLLER AND PILOT GAS VALVE, LIGHTING PILOT.

- THE SENSING PROBE PROVES THE PRESENCE OF THE PILOT FLAME.

- DE-ENERGIZING THE IGNITOR.
- ENERGIZING THE LOW STAGE OF THE GAS VALVE.

- HIGH STAGE OF THERMOSTAT CALLS FOR HEAT.

- ENERGIZING THE HIGH STAGE OF THE GAS VALVE.

- SET THERMOSTAT AT "OFF" POSITION FOR SHUTDOWN.

OPERATING SEQUENCE

8 VA. MAX.

7

8

W1

W2

OPTIONAL

TWO

ST

A

GE THERMOST

AT

R

X-HX-CX-HCX SERIES AH2/AH3-AG2-CL22 WD #274950

BL

HIGH

STG

HI

PV

PIL

O

T

STG

LO

W

C

MV

REDUNDANT

GAS V

AL

VE

HONE

Y

WELL T

WO

ST

A

GE

8

10

OPTIONAL SP-ST

S/W SWITCH

BK

BK

- BLOWER MOTOR IS ENERGIZED AS DETERMINED BY FAN TIME DELAY.

PIL

O

T

AL

TERNA

TE

W

.R.

T

WO

ST

A

GE

REDUNDANT

GAS V

AL

VE

R

BL

3

HIGH

STG

4

BK

STG

2

LO

W

1

BR

(SEE NOTES)

- ON A CALL FOR HEAT, THE BLOWER MOTOR OPERATES FROM FAN TIME DELAY.

BK

- BLOWER MOTOR REMAINS ON AS DETERMINED BY FAN TIME DELAY.

CONTACTS

FAN TD

1

3

TERMINAL BLOCK --
HEATER COMPARTMENT

4, 7, 8, 10, 11, 12, 13, B & W

BL

BK

IGNITION

CONTROLLER

PROBE

GRND

SPARK

FLAME SENSING

MV/PV

GND

GND

MV

SENSE

TH

PV

G

BURNER

GND

BR

Y

ON 115/460V. UNITS THE CONTROL TRANSFORMER IS A SINGLE VOLTAGE PRIMARY.

- ON 208/230V. UNITS THE CONTROL TRANSFORMER HAS A DUAL VOLTAGE PRIMARY.

- USE #14 GA. WIRE FOR LINE AND MOTOR WIRING ON THREE PHASE UNIT.

TO PREVENT VOLTAGE DROP BEYOND FIVE PERCENT OF SUPPLY LINE VOLTAGE.

- LINE AND BLOWER MOTOR BRANCH CIRCUIT WIRE SIZE SHOULD BE OF A SIZE

A TEMPERATURE RATING OF AT LEAST 105 DEGREES C., EXCEPT FOR ENERGY

MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING

- CAUTION: IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE

- DOTTED WIRING AND THE FOLLOWING CONTROLS ARE SUPPLIED AND INSTALLED

- THE FOLLOWING CONTROLS ARE SUPPLIED AS OPTIONAL EQUIPMENT: THERMOSTAT

- THE FOLLOWING CONTROLS ARE SUPPLIED BY REZNOR FOR FIELD INSTALLATION: CONTROL SWITCH

FOR 115/460V. UNITS USE BLACK AND YELLOW LEADS.

FOR 208V. UNITS USE BLACK AND RED LEADS (CAP YELLOW).

FOR 230V. UNITS USE BLACK AND YELLOW LEADS (CAP RED).

CUTOFF OR SENSOR LEAD WIRE WHICH MUST BE 150 DEGREES C.

- USE #18 GA. WIRE FOR 24 VOLT CONTROL WIRING ON UNIT.

BY OTHERS: NONE

NOTES

USE DUAL ELEMENTS TIME DELAY FUSES AND SIZE ACCORDING TO 1.25
TIMES THE MAXIMUM TOTAL INPUT AMPS.

- WHEN PROVIDING OR REPLACING FUSES IN THE FUSIBLE DISCONNECT SWITCH

- DISCONNECT SWITCH IS FIELD FURNISHED OR AVAILABLE FROM FACTORY AS AN OPTION.

C

7

- IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE SAFETY SWITCH CLOSES THE MAIN VALVE. IF THE PILOT IS NOT EXTABLISHED WITHIN
120 SEC. THE UNIT LOCKS OUT FOR ONE HOUR, UNLESS IT IS RESET BY INTERRUPTING POWER
TO THE CONTROL CIRCUIT. (SEE LIGHTING INSTRUCTIONS.)