beautypg.com

0 mechanical (cont'd), 2 venting (cont'd) – Reznor X Unit Installation Manual User Manual

Page 10

background image

Form I-X, P/N 150491 R10, Page 10

6.0 Mechanical

(cont'd)

2. The unit is equipped with a built-in draft diverter, consequently an external draft

diverter

MUST NOT be installed in the vent connector or any internal alterations

made. Do not install a manual damper or other fixed restriction in the vent

connector.

3. Vent pipe should be a minimum of 26-gauge galvanized steel or other non-

corrosive material. Double-wall, Type B vent pipe such as Metalbestos or

Amerivent is recommended. (

NOTE: Double-wall pipe is not available in 9"

diameter.) Where it is necessary to run the vent pipe through an exterior wall of

combustible materials, a suitable thimble must be used. The vent pipe shall have

a clearance of at least six inches (152mm) from combustible materials or as is

specified by the double-wall vent pipe manufacturer.

4. With the outlet on the heater in the horizontal position, it is recommended that a

12-18" (305-457mm) piece of straight pipe be connected to the flue collar before

installing an elbow. The horizontal vent pipe run should have a uniform rise of at

least 1/4" per foot of horizontal run in the direction of discharge. The length of the

lateral run must not exceed lengths shown in the vent tables of the National Fuel

Gas Code or the Canadian Installation Code for Gas Burning Appliances (See Vent

Tables below).

5. Support horizontal runs every six feet (1.8M). Support vertical runs of type

"B" double-wall vent pipe in accordance with the requirements of the pipe

manufacturer. Support single-wall vertical pipe in accordance with accepted

industry practices. Do not rely on the heater for support of either horizontal or

vertical pipes. Use non-combustible supports.

6. Vent connectors serving Category I heaters shall not be connected into any portion

of a mechanical draft system operating under positive pressure.

7. Where it is necessary to use a long run of vent pipe, or where the vent pipe is

exposed to cold air, condensation within the pipe may occur. There are two ways

to overcome or eliminate this problem.

(a) Prevent condensation by insulating the pipe so that the temperature of the flue

products never drops below 250°F.

(b) Use double-wall, Type B vent pipe which is recommended for the reduction or

elimination of condensate problems. Where extreme conditions are present

and condensate is anticipated, install a trap for collecting condensate.

8. The vent connection may be made into a suitable permanent chimney or into a

gas vent. The effective area of the vent connector, gas vent or chimney when

connected to a single appliance shall not be less than the area of the appliance

drafthood outlet or in accordance with approved venting methods. The effective

area of the gas vent or chimney when connected to more than one appliance shall

not be less than the area of the largest vent connector plus 50% of the areas of

additional vent connectors or in accordance with approved venting methods.

Minimum permissible height of the vertical vent is 5 feet (1.5M) providing no

horizontal vent pipe connector is used. If a horizontal vent connector is necessary,

consult Tables below or the National Fuel Gas Code or the Canadian Installation

Code for Gas Burning Appliances, for the maximum permissible length of a

horizontal pipe run (vent connector) for a given vertical height of gas vent.

The gas vent or chimney should extend at least 3 feet (1M) above the highest point

where it passes through a roof of a building and at least 2 feet (.6M) higher than

any portion of a building or obstruction within a horizontal distance of 10 feet (3M).

Install a Reznor Option CC1 vent cap on the end of the vent pipe to prevent rain

or snow from entering the open end. (

NOTE: When installing a Size 125, run the

required 7" vent pipe and use a field-supplied increaser to attach an 8" vent cap.)

9. If the heater is installed in a space served by a large exhaust fan, be sure that the

exhaust fan does not affect the operation of the heater or the satisfactory venting

of its products of combustion.

If a negative pressure exists, as evidenced by a downdraft, a factory-designed

mechanical motor drive venter (Option CA) should be installed. In severe negative

pressure conditions, makeup air equipment may be necessary.

6.2.1 Venting Requirements (cont'd)

6.2 Venting (cont'd)