beautypg.com

0 maintenance and service, 1 maintenance schedule, 0 commissioning and startup (cont'd) – Reznor X Unit Installation Manual User Manual

Page 24

background image

Form I-X, P/N 150491 R10, Page 24

DANGER

The gas burner in this gas-fired equipment is designed and equipped to provide

safe, complete combustion. However, if the installation does not permit the burner

to receive the proper supply of combustion air, complete combustion may not occur.

The result is incomplete combustion which produces carbon monoxide, a poisonous

gas that can cause death. Safe operation of indirect-fired gas burning equipment

requires a properly operating vent system which vents all flue products to the

outside atmosphere. FAILURE TO PROVIDE PROPER VENTING WILL RESULT IN A

HEALTH HAZARD WHICH COULD CAUSE SERIOUS PERSONAL INJURY OR DEATH.

Always comply with the combustion air requirements in the installation codes and in

Paragraph 2.2. Combustion air at the burner should be regulated only by manufacturer-

provided equipment. NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY OF

COMBUSTION AIR TO ANY HEATER. Indoor units installed in a confined space must be

supplied with air for combustion as required by Code and in Paragraph 2.2 of this heater

installation manual. MAINTAIN THE VENT SYSTEM IN STRUCTURALLY SOUND AND

PROPERLY OPERATING CONDITION.

Close all panels tightly. With the heater on, check limit control by completely block-

ing off distribution air. The limit control should open within a few minutes, shutting

off the gas supply to the main burners.

Place "Literature Bag" containing Limited Warranty Card, this booklet, and any

optional information in an accessible location near the heater. Follow the instruc-

tions on the bag

10.0 Maintenance

and Service

WARNING

If you turn off the power supply, turn off the gas. See Hazard Levels,

Page 2.

This unit will operate with a minimum of maintenance. To ensure long life and satis-

factory performance, a furnace that is operating under normal conditions should be

inspected every four months. If the furnace is operating in an area where an unusual

amount of dust or soot or other impurities are present in the air, more frequent inspec-

tion is recommended.
The following procedures should be carried out at least annually (See Para-

graphs 10.2.1- 10.2.4 for specific instructions.):

Clean all dirt and grease from the primary and secondary combustion air openings.

Check the gas valve to ensure that gas flow is being shutoff completely.

Clean the heat exchanger both internally and externally.

Check the pilot burner and main burners for scale, dust, or lint accumulation. Clean

as needed.

Check the vent system for soundness. Replace any parts that do not appear

sound.

Check the wiring for any damaged wire. Replace damaged wiring. (See the wiring

diagram for replacement wiring requirements.)

CAUTION: When cleaning, wearing eye protection is recommended.

NOTE: Use only factory-authorized replacement parts.

10.1 Maintenance

Schedule

9.0 Commissioning

and Startup

(cont'd)

9.3 Check installation after startup (cont'd)