beautypg.com

A) (b), 0 controls (cont'd), 4 gas controls (cont'd) – Reznor X Unit Installation Manual User Manual

Page 20

background image

Form I-X, P/N 150491 R10, Page 20

Makeup air applications are usually adjusted to discharge an outlet air temperature

between 65°F and 75°F. In all applications, the allowable temperature rise of the fur-

nace in the installation dictates the limits of the ductstat temperature setting.
Depending on the option selection, the sensor is either connected by capillary tubing to

the unit-mounted ductstat (

FIGURES 18 and 19) or electrically connected to a remote

electronic temperature selector (

FIGURE 20). See Paragraph 6.3.5 for instructions on

locating the sensor in the ductwork.
Optional Ductstat with Capillary Tubing (FIGURE 18) - The control is set to 70°F

and has an adjustable range with a fixed differential of 2-1/2°F. Due to different CFM

settings and outside air temperatures, the average downstream outlet temperature

may not match the ductstat setting exactly. After the installation is complete, adjust the

setpoint of the ductstat to achieve the desired average discharge air temperature.

Adjustable range

0-100°F with a fixed

differential of 3°F.

FIGURE 18A - Ductstat

Control in Option AG3

FIGURE 18B -

Ductstat Bulb

Location (factory

installed)

Ductstat Bulb

in Option AG3

Model X Duct Furnace

Front (Discharge) View

FIGURE 19 - Ductstat

Control in Two-Stage

Makeup Air Control

Option AG15 -

(A) Remote

Temperature Selector;

(B) Stage-Adder

Module

(A)

(B)

Optional Ductstat with Electronic Remote Setpoint

Module (Option AG15) - The sensing probe is field-

wired to a remote temperature selector. The temper-

ature selector has an operating range to 120°F. The

remote modules are shipped separately for field instal-

lation.
Follow the wiring diagram with the unit and the manu-

facturer's instructions for wiring and installation.
There will be one module for selecting temperature and

one-stage adder module as illustrated in

FIGURE 20.

CAUTION: Be sure heat/cool selector

switch is set at "Heat" position.

8.4.4 Optional

Electronic Modulation

The type and capability of the electronic modulation system depends on the option

selected. Electronic modulation options are identified by a suffix to the Serial No.

printed on the heater rating plate. AG7 is identified as MV-1; AG8 is identified as MV-3;

AG9 is identified as MV-4; and AG21 is identified as MV-A.
Electronic Modulation between 50% and 100% Firing Rate (Options AG7, AG8,

AG9) - Depending on the heat requirements as established by the thermistor sensor,

the burner modulates between 100% and 50% firing. The thermistor is a resistor that

is temperature sensitive in that as the surrounding temperature changes, the Ohms

resistance changes through the thermistor. This change is monitored by the solid state

control center (amplifier) which furnishes varying DC current to the modulating valve to

adjust the gas input.
Each modulating valve is basically a regulator with electrical means of raising and

lowering the discharge pressure. When no DC current is fed to this device, it functions

as a gas pressure regulator, supplying 3.5" w.c. pressure to the main operating valve.
Refer to the wiring diagram supplied with the furnace for proper wiring connections. Elec-

tronic modulation for heating controlled by a specially designed room thermostat (60°-

85°F) is identified as Option AG7. Electronic modulation control systems for makeup

air applications controlled by a field-installed duct sensor (See Paragraph 6.3.5.) and

temperature selector (55-90°F) are identified as either Option AG8 or Option AG9.

The temperature selector setting for Option AG8 is on the amplifier; Option AG9 has a

remote temperature selector. Both systems are available with an override thermostat.

8.0 Controls

(cont'd)

8.4 Gas Controls

(cont'd)

8.4.3 Optional Two-

Stage Operation for

Makeup Air (cont'd)

Factory

set at

70°F

FIGURE 20A -

Amplifier in Options

AG7, AG8, and AG9