2 dimensions, 0 mounting, Figure 1 - dimensions (inches and mm) – Reznor RDF Unit Installation Manual User Manual
Page 5
I-RDF, PN148384R5, Page 5
4.2 Dimensions
FIGURE 1 - Dimensions (inches and mm)
Top
View
Control
Side
Front View
Rear View
A
(Full Length of Outside of Curb Cap)
D
(Inside of Curb Cap)
Z
Y
B
(Cabinet
Height)
2-5/8 (67)
Control
Compartment*
Blower
Compartment
Supply Wiring**
24V Wiring**
E
(Inside Width of Curb Cap)
X
U
W
T
V
C
(Cabinet Width)
1 (25)
Horizontal
Discharge
(T x U )
S
R
Outside Air
Opening
(R x S)
See Outside Air Hood or
Filter Cabinet Dimensions
on page 11.)
N
L
P
Q
M
G
K
J
F
H
Optional Return
Air
Opening (F x G)
Bottom
Discharge
(L x M)
3 (76)
Gas Supply
(Y and Z)
Dimensions (inches)
Model Sizes
A
B
C
D
E
F
G
H
J
K
L
M
1-20-3, 1-40-3,
1-50-3, 1-65-3
88
37-1/8
44-3/16 84-13/16 45-1/2 24-1/2 10-1/2 5-7/16 14-9/32 15-5/8 21-29/32
19-1/8
2-80-3, 2-120-3
88
48-11/16 68-1/4 84-13/16 69-1/2
52
16-1/4 5-5/16 10-15/16 15-1/2 27-9/32
27-7/32
3-180-3, 3-260-3 135-3/4
61-5/8
82-9/16 132-9/16 83-1/8 64-9/16 19-1/16 5-5/32 13-13/32 21-5/8
37
37-3/32
Model Sizes
N
P
Q
R
S
T
U
V
W
X
Y
Z
1-20-3, 1-40-3,
1-50-3, 1-65-3
7-11/16
14-5/8
12-5/8
31-1/8
31-1/8 21-3/4 18-3/4
7-3/4
5-1/4
13-1/8
8-9/16
42-7/32
2-80-3, 2-120-3
16-5/16 24-21/32 11-7/32 55-3/16
42-5/8 27-1/4 27-1/4 16-5/32 6-11/32 15-3/32
8-3/4
48-15/16
3-180-3, 3-260-3 14-9/16 31-9/16
7-7/16
67-1/8
55-9/16 36-3/4 36-3/4 14-7/16
4
20-7/8 8-11/16
56
Dimensions (mm)
Model Sizes
A
B
C
D
E
F
G
H
J
K
L
M
1-20-3, 1-40-3,
1-50-3, 1-65-3
2235
943
1122
2154
1156
622
267
138
363
397
556
486
2-80-3, 2-120-3
2235
1237
1734
2154
1765
1321
413
135
278
394
691
691
3-180-3, 3-260-3
3448
1565
2097
3367
2111
1640
484
131
341
549
940
942
Model Sizes
N
P
Q
R
S
T
U
V
W
X
Y
Z
1-20-3, 1-40-3,
1-50-3, 1-65-3
195
371
321
791
791
552
476
197
133
333
217
1072
2-80-3, 2-120-3
414
626
285
1402
1083
692
692
410
161
383
222
1243
3-180-3, 3-260-3
370
802
189
1705
1411
933
933
367
102
530
221
1422
* RDF-2 and RDF-3 sys-
tems have double hinged
doors as illustrated. Control
compartment on RDF-1 has
a single hinged door.
** Configuration is for
RDF-2 and RDF-3. The
supply connection on the
RDF-1 systems is above the
control wiring connection.
5.0 Mounting
Mounting the system is the responsibility of the installer. Verify that the supporting
structure has sufficient load-carrying capacity to support the weight.
Depending on the building and its use, determine whether or not additional measures
should be taken to reduce the effect of blower vibration and/or noise.
When selecting a location for an outdoor installation, position the unit so that the air
inlet will
NOT be facing into the prevailing wind. A minimum of 14" (356mm) clearance
is required from the bottom of the air inlet hood to the mounting surface.
Prior to installation, be sure that the method of support is in agreement with all local
building codes. For both indoor and outdoor installations, check for service platform
requirements. If an outdoor system is being installed with bottom discharge and/or
return air, a full perimeter roof curb is recommended.