4.0 Dimensions
& Clearances
(cont'd)
WARNING
Units must be level for proper operation. Do not place or add additional
weight to the suspended furnace. See Hazard Levels, page 2.
5.0 Suspending or
Mounting the
Furnace
Before installing the furnace, check the supporting structure to be used to verify that it
has sufficient load-carrying capacity to support the weight of the unit.
Service and combustion air clearances apply to both suspended and mounted heater.
Net Weight by Size
Size
75
100
125
140
170
200
225
250
300
350
400
Lbs
104
104
126
128
150
172
194
216
262
306
328
kg
47
47
57
58
68
78
88
98
119
139
149
5.1 Weights
The furnace is provided with four 15/32" (12mm) diameter holes to provide four-point
suspension. To suspend the unit, use 7/16"-16 threaded rod and the hardware shown
in
FIGURE 6A. See FIGURE 6A, right side, for details. NOTE: A hanger adapter kit
Option CK3 with swivels for 1" pipe is available. See
FIGURE 6B.
5.2 Suspending the
Furnace
Centerline of Hangers
A
16
(406mm)
15/32 (12mm)
Diameter Holes
7/16 Diameter
Threaded Rod
Nut for 7/16 Rod
15/32 (12mm)
Diameter Hole
Hanger
Split Ring Lockwasher
Nut for 7/16 Rod
Front View
Side V
iew
FIGURE 6B - Option CK3
Hanger Kit (P/N 57959) with
four threaded sockets
Free-turning threaded
socket (1" pipe)
FIGURE 6A -
Suspending a
Single Furnace
5.3 Mounting the
Furnace
Standard position
of hanger bracket.
To base mount,
remove hanger
bracket and
re-locate to
position below.
Re-locate hanger
bracket to this
location when base
mounting heater.
Access
Panel in
Duct
Access
Panel in
Duct
Limit Control
(on discharge
side of unit)
Airflow
Combustion Air Inlet
Combustion
Air Inlet
6 (152mm)
minimum
clearance
10 (254mm)
12 (305mm) clearance
to combustibles required
from furnace bottom
Keep area clean and
maintain 29 (737mm)
clearance for burner
rack service.
FIGURE 7 -
Base-
Mounted
Furnace
Required Clearances
Front
Top
Flue Connector
Sides Bottom
Rear
6"
6"
6"
12"
12"
29"
152mm
152mm
152mm
305mm
305mm
737mm
Change position of the
hanger bracket as shown in
FIGURE 7.
When the furnace is
mounted on combustible
material, a minimum
clearance of 12" (305mm)
is required.
4.2 Clearances (cont'd)
"A"
Size
inches
mm
75-100
14-5/8
371
125-140 17-3/8
441
170
20-1/8
511
200
22-7/8
581
225
25-5/8
651
250
28-3/8
721
300
33-7/8
860
350
39-3/8 1000
400
44-7/8 1140