UG_6612_ 017
6612_OMU_S2+2_URT_V1_14 Firmware Description Document
Rev. 1.0
45
MPU
Parameter
Location
(hex)
LSB
Default
Comment
Example
PFA_nb_Pos
Threshold
DB
–
+0.700
Narrowband Power Factor
Positive Threshold for Outlet 1. A
narrowband power factor less
than this threshold will set an
alarm (bit 10 of the Alarm Status
Register).
If the positive narrowband
power factor threshold on
Outlet 1 is to be changed
from the default to +0.600
then set as follows:
)DB=+0.600
PFA_wb_Neg
Threshold
DC
–
-0.700
Wideband Power Factor Negative
Threshold for Outlet 1. A less
negative wideband power factor
than this threshold will set an
alarm (bit 11 of the Alarm Status
Register). Only available if )F2 bit
2 is set to 1.
If the negative wideband
power factor threshold on
Outlet 1 is to be changed
from the default to -0.6 then
set as follows:
)DC=-0.600
PFA_wb_Pos
Threshold
DD
–
+0.700
Wideband Power Factor Positive
Threshold for Outlet 1. A positive
wideband power factor less than
this threshold will set an alarm (bit
12 of the Alarm Status Register).
If the positive wideband
power factor threshold on
Outlet 1 is to be changed
from the default to +0.6
then set as follows:
)DD=+0.600
Peak IB_nb
Alarm
Threshold
DE
mArms
+15.000
Maximum Narrowband Current
measured on the IB channel
above which a flag must set (bit
13 of the Alarm Status Register).
If the peak narrowband
current threshold on Outlet
2 is to be changed from the
default value of 15 Amps to
30 Amps then set as
follows:
)DE=+30.000
Peak IB_wb
Alarm
Threshold
DF
mArms
+15.000
Maximum Wideband Current
measured on the IB channel
above which a flag must set (bit
14 of the Alarm Status Register).
If the peak wideband
current threshold on Outlet
2 is to be changed from the
default value of 15 Amps to
30 Amps then set as
follows:
)DF=+30.000
PFB_nb_Neg
Threshold
E0
–
-0.700
Narrowband Power Factor
Negative Threshold for Outlet 2.
A less negative narrowband
power factor than this threshold
will set an alarm (bit 15 of the
Alarm Status Register). Only
available if )F2 bit 2 is set to 1.
If the negative narrowband
power factor threshold on
Outlet 2 is to be changed
from the default to -0.6 then
set as follows:
)E0=-0.600
PFB_nb_Pos
Threshold
E1
–
+0.700
Narrowband Power Factor
Positive Threshold for Outlet 2. A
narrowband power factor less
than this threshold will set an
alarm (bit 16 of the Alarm Status
Register).
If the positive narrowband
power factor threshold on
Outlet 2 is to be changed
from the default to +0.600
then set as follows:
)E1=+0.600