6612_OMU_S2+2_URT_V1_14 Firmware Description Document

UG_6612_017

20

Rev. 1.0

5 MPU Measurement Outputs

This section describes the measurement outputs that can be obtained. Energy outputs are accumulated
numbers. The host accessing the measurement information from the 78M6612 more frequently will not
result in any update in the information.

Table 2 lists the Narrowband outputs for Outlet 1.

Table 2: Outlet 1 MPU Outputs for Narrowband Method

Output

Location

(hex)

LSB

Comment

Example

Delta

Temperature

00

0.1 °C

Temperature difference from 22 °C.

If external temperature is 32 °C

)00?

Returns:

+10.0

Line

Frequency

01

0.01 Hz

Line Frequency.

If the line frequency is 60 Hz:

)01?

Returns:

+60.00

Alarm Status

02

Bit 0 – Minimum Temperature Alarm.

Definition for Status Register

Bit 1 – Maximum Temperature

Alarm.

Bit 2 – Minimum Frequency Alarm.

Bit 3 – Maximum Frequency Alarm.

Bit 4 - SAG Voltage Alarm.

Bit 5 – MINVA

under minimum

voltage on VA input.

Bit 6 – MAXVA

over maximum

voltage on VA input.

Bit 7 – MAXIA_NB

maximum

narrowband current exceeded on

Outlet 1.

Bit 8 – MAXIA_WB

maximum

wideband current exceeded on

Outlet 1.

Bit 9 – PFA_NB negative –

Narrowband Power Factor Negative

Threshold Alarm for Outlet 1. Only

available is )F2 bit 2 is 1.

Bit 10 – PFA_NB positive

Narrowband Power Factor Positive

Threshold Alarm for Outlet 1.

Bit 11 – PFA_WB negative -

Wideband Power Factor Negative

Threshold Alarm for Outlet 1. Only

available is )F2 bit 2 is 1.

Bit 12 – PFA_WB positive

Wideband Power Factor Positive

Threshold Alarm for Outlet 1.

Bit 13 – MAXIB_NB

maximum

narrowband current exceeded on

Outlet 2.

Bit 14 – MAXIB_WB

maximum

wideband current exceeded on

Outlet 2.



Alarms become “1” when

thresholds exceeded.

Note: Additional Status Alert is

Located at addr 0xBD

(see

Table 8

)

Note: When AC voltage input is

less than or equal to 10 V

RMS

,

Only MINVA alarm is active.

All measurements are
forced to 0 except power
factor, which is forced to 1.

Note: The frequency

measurement is forced to 0 as

long as the SAG voltage alarm

is active.