beautypg.com

Electrical connections, Interfacing, Setup and calibration – Flintec FAD-40 User Manual

Page 37: Modbus rtu (for fad-40mb only)

background image

FAD-40 Technical Manual, Rev. 1.06 December 2012

Page 37 of 52

6.2. Electrical Connections

RS-485 connection is shown in figure 6.2.

Figure 6.2

– FAD-40 / FAD-40MB serial interface connection

RS-485 Serial Interface

Use

Interfacing with PC or PLC, setup via xFace

Data format

BSI (default for FAD-40), Modbus RTU (for FAD-40MB only, default)

Baud rate

1200 / 2400 / 4800 / 9600 (Default) / 19200 / 38400 / 57600 bps

Length and parity

8 None 1 (default), 7 odd 1, 7 even 1

Start / Stop bits

1 start bit and 1 stop bit

Warning: Connect the shield to the reference ground.
Warning: Disconnect xFace PC software for Modbus-RTU interfacing

Load Cell Connection

See chapter 4.2.2

Digital I/O Connection

See chapter 4.2.3

Power Supply Connection

See chapter 4.2.1

6.3. Interfacing

FAD-40 and FAD-40MB instruments have one serial interface connector on the front of the instrument: RS-485.
The table below describes the data format for interfacing the peripherals and their application:

Data Format

Description

Application

Hardware

BSI

Demand interface on BSI
Serial Interface format.
Refer to chapter 5.10

Master

– Slave data interfacing with

PLC or PC.

RS-485

Modbus RTU
(FAD-40MB only)

Modbus RTU interfacing.
Refer to chapter 5.11

Interfacing with PLC.

RS-485

Table 6.1

– Data output interfacing

Attention: Please disable the interface if not used to increase the performance of the instrument.

6.4. Setup and Calibration

FAD-40 and FAD-40MB instruments are set up and calibrated by xFace. The A/D Converter settings are very
important for a good weighing performance. Please refer to chapter 5.3.

6.5. Modbus RTU (for FAD-40MB only)

If the FAD-40MB instrument is setup for Modbus, it can be used as a Modbus RTU slave in a RS-485
communication netw

ork. Function codes „0x03‟ and „0x10‟ are supported. For RS-485 setup please refer to

chapter 5.3.2, for the Modbus data structure please refer to chapter 5.11.