Fad-40px output to plc input 3, Dword – Flintec FAD-40 User Manual
Page 29
FAD-40 Technical Manual, Rev. 1.06 December 2012
Page 29 of 52
FAD-40Px Output to PLC Input 3
rd
Dword
Bit no.
3
rd
Dword Description
D31…D21 Not in use
D20
Input for I/O2
D19
Input for I/O3
D18
Output for I/O3
D17
Output for I/O2
D16
Output for I/O1
D15…D12
Error codes of
converter
0000
No error found
0001
ADC out
0010
ADC over
0011
ADC under
0100
System error
0101
In setup mode
0110
Low/High voltage error
0111
Instrument not found
D11…D10 Not in use
D9
Operation mode
0
Weight & Force Mode
1
Count Mode
D8
Zero range
0
Weight is out of zero range
1
Weight is in of zero range
D7
Indication
0
Gross
1
Net
D6
MD
–
Motion detection
0
Stable
1
Unstable
D5
D4
D3
D2
D1
Read command
response
00000
Indicated weight
00001
Gross weight
00010
Tare weight
00011
Indicated weight (floating point type)
00100
Gross weight (floating point type)
00101
Tare weight (floating point type)
10000
Calibration Status (Refer to table 8.2)
D0
CMD flag
A change of Flag indicates: The command is applied successfully