Hardware configuration hint, Fad-40px output to plc input, Fad-40px output to plc input 2 – Flintec FAD-40 User Manual
Page 28: Dword, Calibration status
FAD-40 Technical Manual, Rev. 1.06 December 2012
Page 28 of 52
5.11. Profibus and ProfiNet Data Structure (for FAD-40Px only)
Hardware Configuration Hint
To install the FAD-40PB or FAD-40PN into the PLC Hardware Configuration use the GSD file memory parts to
create exactly the following memory structure:
Input 2 Words
Output 2 Words
Input 2 Words
Input 2 Words
Output 2 Words
Output 2 Words
FAD-40Px Output to PLC Input
Dword
D31 D30 D29 D28
D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
D15 D14 D13 D12
D11 D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
1st
Dword
Reserved
2nd
Dword
W31
MSB
W30 W29 W28 W27 W26 W25 W24 W23 W22 W21 W20 W19 W18 W17 W16
W15 W14 W13 W12 W11 W10
W9
W8
W7
W6
W5
W4
W3
W2
W1
W0
LSB
3rd
Dword
Not in use
I/O2
in
I/O3
in
I/O3
out
I/O2
out
I/O1
out
Error codes of converter
Not in use
Op.
mode
Zero
range
Gross
Net
MD
Read command response
Cmd
Flag
FAD-40Px Output to PLC Input 2
nd
Dword
The 2
nd
Dword contains the weight value respective the calibration information according to the
“read command
response” (Refer to PLC Output to FAD-40Px Input 3rd Dword).
Calibration Status
Bit no.
2
nd
Dword descriptions when read command is ‘Calibration Status’.
Refer to PLC Output to FAD-40Px Input 3
rd
Dword
D31…D16 Not in use
D15…D8
Calibration
error
0000 0001
Calibration timeout: - Restart calibration
0000 0010
ADC error: - Re-energize the instrument
0000 0011
Instrument cannot be calibrated
- Check load cell cable; - Re-energize the instrument
0010 0010
Instrument cannot be calibrated
- Load cell signal is very low or too high
0010 0011
Calibration Error
- Calibration test weight is too small; Increase calibration weight
value (Write test weight value from PLC Output to FAD-30Px
Input 2
nd
Dword then restart the calibration)
- Check load cell connections
0010 0101
Scale unstable: - Wait until scale becomes stable
- Check ground wiring
D7...D0
Calibration
process
status
0000 0001
System ready for calibration
0000 0011
Zero calibration in process
0000 0100
Span calibration in process
0000 1001
Error (Calibration error)