FAD-40 Technical Manual, Rev. 1.06 December 2012

Page 28 of 52

5.11. Profibus and ProfiNet Data Structure (for FAD-40Px only)

Hardware Configuration Hint

To install the FAD-40PB or FAD-40PN into the PLC Hardware Configuration use the GSD file memory parts to
create exactly the following memory structure:

Input 2 Words

Output 2 Words

Input 2 Words

Input 2 Words

Output 2 Words

Output 2 Words

FAD-40Px Output to PLC Input

Dword

D31 D30 D29 D28

D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16

D15 D14 D13 D12

D11 D10

D9

D8

D7

D6

D5

D4

D3

D2

D1

D0

1st
Dword

Reserved

2nd
Dword

W31

MSB

W30 W29 W28 W27 W26 W25 W24 W23 W22 W21 W20 W19 W18 W17 W16

W15 W14 W13 W12 W11 W10

W9

W8

W7

W6

W5

W4

W3

W2

W1

W0

LSB

3rd
Dword

Not in use

I/O2

in

I/O3

in

I/O3

out

I/O2

out

I/O1

out

Error codes of converter

Not in use

Op.

mode

Zero

range

Gross

Net

MD

Read command response

Cmd

Flag

FAD-40Px Output to PLC Input 2

nd

Dword


The 2

nd

Dword contains the weight value respective the calibration information according to the

“read command

response” (Refer to PLC Output to FAD-40Px Input 3rd Dword).

Calibration Status

Bit no.

2

nd

Dword descriptions when read command is ‘Calibration Status’.

Refer to PLC Output to FAD-40Px Input 3

rd

Dword

D31…D16 Not in use

D15…D8

Calibration
error

0000 0001

Calibration timeout: - Restart calibration

0000 0010

ADC error: - Re-energize the instrument

0000 0011

Instrument cannot be calibrated
- Check load cell cable; - Re-energize the instrument

0010 0010

Instrument cannot be calibrated
- Load cell signal is very low or too high

0010 0011

Calibration Error
- Calibration test weight is too small; Increase calibration weight
value (Write test weight value from PLC Output to FAD-30Px
Input 2

nd

Dword then restart the calibration)

- Check load cell connections

0010 0101

Scale unstable: - Wait until scale becomes stable
- Check ground wiring

D7...D0

Calibration
process
status

0000 0001

System ready for calibration

0000 0011

Zero calibration in process

0000 0100

Span calibration in process

0000 1001

Error (Calibration error)