Installing the Cisco Nexus 5010 Chassis in a Cabinet or Rack
Installing the Cisco Nexus 5010 Chassis in a Cabinet or Rack
This section describes how to use the rack-mount kit provided with the switch to install the Cisco Nexus
5010 switch into a cabinet or rack that meets the requirements described in
All Cisco Nexus 5000 switches use the same installation procedure.
Caution
If the rack is on wheels, ensure that the brakes are engaged or that the rack is otherwise stabilized.
lists the items contained in the rack-mount kit provided with the switch.
To install the switch in a cabinet or rack using the rack-mount kit provided with the switch, follow these
steps:
Step 1
Install the front rack-mount brackets as follows:
a.
Position a front rack-mount bracket against the chassis and align the screw holes as shown in
. Then attach the front rack-mount bracket to the chassis with six of the M4 screws.
b.
Repeat with the other front rack-mount bracket on the other side of the switch.
Figure 3-7
Attaching Front Rack-Mount Bracket to the Cisco Nexus 5010 switch
Table 3-3
Cisco Nexus 5010 Switch Rack-Mount Kit
Quantity
Part Description
2
Rack-mount brackets
12
M4x0.7 x 8-mm Phillips countersunk screws
2
Rack-mount guides
10
10-32 Rack Nuts
10
10-32 x 3/4-inch Phillips countersunk screws
2
Slider rails
(21 inch minimum to a 33 inch maximum