beautypg.com

Figure 6.10, Grounding terminal location, Maintenance – AERCO KC1000 Heater Mar 2011 User Manual

Page 52

background image

MAINTENANCE

6-8

The following parts will be necessary for reassembly after inspection:

GP-122537

Exhaust Manifold to

Combustion Chamber

Gasket

GP-18900

Manifold to Tubesheet

Gasket

124749

Lower Burner Gasket

124834

Upper Burner Gasket

*124839

Combustion Chamber Liner

*Not necessary to change but should be on hand in the event damage occurs during the inspection.

To remove the manifold for inspection:

1. Disconnect AC power and turn off the gas supply to the unit.

2. Remove the sheet metal covers from the unit.

3. Disconnect the plastic tubing from the condensate cup to drain and remove the rear covers.

4. Remove the condensate cup from under the unit and the condensate drainage tubing from the

manifold.

5. Disconnect the flame detector and ignition cable wires from the flame detector and igniter contactor.

Remove the flame detector and igniter as per paragraphs 6.2, and 6.3.

6. Remove the grounding terminal from the burner by loosening the upper screw and sliding the

connector from the grounding rod, (See Figure 6.10).

GROUND

TERMINAL

UPPER

SCREW

LOWER

BURNER

SHELL

FLAME

DETECTOR

IGNITER

GND WIRE FROM

TRANSFORMER

Figure 6.10

Grounding Terminal Location

7. Loosen the 1/4” NPT union on the low NOx staged ignition assembly (Figure 6.11).

8. Disconnect the staged ignition assembly 1/8” elbow from the 3” long NPT nipple at the bottom of the

burner shell.

9. Remove the 3” long NPT nipple and 1/4” O.D. tube (Figure 6.11) from the burner shell.