Figure 5.6, Ssov actuator cover screw location, 10 purge switch open during purge – AERCO KC1000 Heater Mar 2011 User Manual

Page 43: Figure 5.7, Air/fuel valve cover location, 11 ignition switch open during ignition, Safety device testing

background image

SAFETY DEVICE TESTING

5-5

SSOV

ACTUATOR

COVER

SSOV

COVER

SCREW

Figure 5.6

SSOV Actuator Cover Screw Location

5.10 PURGE SWITCH OPEN DURING

PURGE

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and

set the valve position between 25% and

30%.

2. Remove the air/fuel valve cover by rotating

the cover counterclockwise to unlock it and

then pulling it towards you. See Fig. 5.7.

3. Remove one of the two wires from the purge

switch (Fig. 5.8) and start the unit.

4. The unit should begin to start, then shut

down and display PRG SWITCH OPEN

DURING PURGE.

5. Replace the wire on the purge switch and

depress the

CLEAR button. The unit should

restart.

VALVE

COVER

Figure 5.7

Air/Fuel Valve Cover Location

5.11 IGNITION SWITCH OPEN DURING

IGNITION

1. Set the unit’s

ON/OFF switch to the OFF

position. Place the unit in manual mode and

set the valve position between 25% and

30%.

2. Remove the air/fuel valve cover (Fig. 5.7) by

rotating the cover counterclockwise to

unlock it then pulling it towards you.

3. Remove one of the two wires from the

ignition switch (Fig. 5.8) and start the unit.

4. The unit should begin to start and then shut

down and display IGN SWITCH OPEN

DURING IGNITION.

5. Replace the wire on the ignition switch and

depress the

CLEAR button. The unit should

restart.