beautypg.com

5 unit reassembly, 6 temperature control calibration, Initial start-up – AERCO KC1000 Heater Mar 2011 User Manual

Page 36

background image

INITIAL START-UP

4-8

22. Wait for the analyzer to settle and then

compare the new oxygen reading to Table 6

(or 6A). Repeat the inlet air shutter

adjustment until the oxygen is within the

specified range. Also, ensure that the CO

and NOx emissions do not exceed the

values shown. Firmly tighten the inlet air

shutter locking nuts when finished.

REMINDER:

At 30% valve position, adjust only the differential

pressure regulator. At 100% valve position,

adjust only the inlet air shutter.

23. If the measured oxygen reading is above the

oxygen range in Table 6 (or 6A), loosen the

two 7/16" locking nuts securing the inlet air

shutter. Close the air shutter 1/4” to 1/2” to

decrease the oxygen level and tighten the

two nuts.

24. Allow the analyzer to settle then compare

the new oxygen reading to Table 6 (or 6A).

25. Repeat the adjustment until the oxygen is

within the specified range. Also, ensure that

the CO and NOx readings do not exceed the

values shown. Firmly tighten the inlet air

shutter locking nuts when finished.

NOTE:

Adjust the inlet air shutter only at 100% valve

position. Do Not adjust the differential pressure

regulator.

26. Change the valve position to 30%. Allow

time for the combustion analyzer to settle.

Check the measured oxygen level, CO and

NOx emissions to ensure that they are still

within the ranges shown in Table 4.

27. Continue these procedures until all oxygen

levels are within the ranges specified in

Tables 4, 5 and 6 (or 6A).

28. Record all readings on the AERCO start-up

sheet provided with each unit. Proceed to

paragraph 4.5 when all propane combustion

calibration procedures are completed.

4.5 UNIT REASSEMBLY

Once combustion calibration is set properly, the

unit can be re-assembled for permanent

operation.

1. Set the

ON/OFF switch to the OFF position.

Disconnect the AC power supply from the

unit.

2. Shut off the gas supply to the unit.

3. Remove the differential pressure regulator

cap and cap gasket (see Figure 4.3).

4. Apply a drop of silicone adhesive to the

regulator adjusting screw to lock its setting.

5. Reinstall the cap and gasket on the

regulator. Tighten the cap using a

screwdriver or wrench.

6. Remove all of the manometers and barbed

fittings and reinstall the pipe plugs using a

suitable thread compound.

7. Remove the combustion analyzer probe

from the vent hole. Seal the probe hole and

replace the vent connection cover.

8. Replace the unit’s panels and hood.

4.6 TEMPERATURE CONTROL

CALIBRATION

Although the unit comes factory set and

calibrated for a 130

°

F setpoint it is usually

necessary to recalibrate temperature control.

There are two primary adjustments for

performing temperature calibration. These are

Min Load Adj and Max Load Adj (minimum and

maximum load adjustment).

Adjustments to these settings are made at

minimum and maximum load conditions and

should be made in small increments from 1 to 3

degrees. After making an adjustment, the outlet

water temperature must be allowed to settle for

several minutes prior to making any further

adjustments.

When calibrating temperature control, observe

the following:

1. The unit must be in the Auto mode of

operation.

2. The Outlet Feedback option in the Tuning

Menu must be off while performing

calibration.

3. Monitor the

OUTLET TEMPERATURE

display and

VALVE POSITION bar-graph

display to set load conditions and see the

effect of adjustments.

4. Perform the calibration using the Tuning

Menu of the Control Box.