beautypg.com

Aerco, Appendix f, Legend – AERCO KC1000 Heater Mar 2011 User Manual

Page 103: Sd -a -707

background image

APPENDIX F

F-3

CONNECT

5/

8"

I.D

. HOSE TO CONDENSATE DRAIN

SHELL DRAIN VALVE

*

RELIEF VALVE

*

HOUSE RECIRCULATION

(NOTE

6)

6

TAP FOR OXYGEN

MANDATORY GAS PRESSURE REGULATOR

7.

7"

W

.C

. (

PROPANE GAS

) AT MAXIMUM BTU

/H INPUT

GAS IN

- SEE GF

-1030

FOR

MAINTAIN A REGULATED

8.

8''

W

.C

. PRESSURE

(NATURAL GAS

)/

(SUPPLIED BY OTHERS

)

1-

1/

4"

MANUAL SHUTOFF

*

DIRT TRAP

2

ANALYZER

DRAIN

T

T

SIZE INLET FOR

TEMPERATURE RISE

SET AT FLOW CAPACITY

THROTTLING VALVE

T

6

(NOTE

6)

CONNECTION

HOSE

COLD WATER IN

3:

1

PREFERRED

DIA

. RATIO

: 2

:1

MIN

.,

TANK HEIGHT TO

HOT WATER OUT

GAS PIPING INSTALLATION

OF HEATER AT REQUIRED

DIA

. =

2/

3

TANK DIA

.

INLET BAFFLE

FLOW

<

2

FT

/SEC

PUMP

(SEE NOTE

7)

EXPANSION TANK

TEMPERATURE

SWITCH (NOTE

8)

6)

LOCATE WATER INLET AND OUTLET FITTINGS

(i.

e.

UNIONS

, ELBOWS

, ETC

.)

A MINIMUM OF

6"

FROM WATER HEATER

5)

HOSE CONNECTION AT HEATER OUTLET IS FOR INITIAL HEATER CALIBRATION DURING START

-UP

.

4)

THIS IS A TYPICAL INSTALLATION DRAWING

. LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED

.

TO PERMIT THE FLUIDS TO DRAIN FREELY

, BY GRAVITY

, TO A FLOOR DRAIN

.

2)

SHELL DRAIN VALVE AND CONDENSATE HOSE SHOULD BE ARRANGED

1)

FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS

3)

ALL

(*)

ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT

.

RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT

18

" ABOVE THE FLOOR

.

TO THE HEATER

, SEE DIMENSIONAL DRAWING

NOTES

:

CHECK VALVE

LEGEND

STOP VALVE

DRAIN VALVE

UNION

7)

PUMP SHOULD BE CAPABLE OF HEATER

'S RATED FLOW AT DESIGN TEMPERATURE RISE

.

8)

MOUNT TEMPERATURE SWITCH

1/

3

UP FROM THE BOTTOM OF THE TANK

, SWITCH WILL TURN PUMP ON AND OFF

.

GAS FIRED WATER HEATER

KC

1000 1

MIL

. BTU LOW NOx

STRATIFIED STORAGE TANK INSTALLATION

NORTHVALE

, NJ

07647

INTERNATIONAL

, INC

.

APPD

.

DWN

.BY

SCALE

DATE

DATE

JK

NTS

113006

AERCO

SD

-A

-707

D

REV

.

THERMOMETER

T

BALANCING VALVE

RELIEF VALVE

(WHEN EMPLOYED

)

BACKFLOW PREVENTER

VACUUM BREAKER

VACUUM BREAKER (NOTE

12

)

10

) IF PERMITTED BY LOCAL CODES

, A CHECK VALVE MAY BE USED IN PLACE OF A BACKFLOW PREVENTER

.

(NOTE

10

)

11

) CONSULT LOCAL CODES FOR PROPER TYPE OF CONNECTIONS TO STORAGE TANK

.

12

) WHEN REQUIRED BY LOCAL CODES

, A VACUUM BREAKER MUST BE INSTALLED WITH THE STORAGE TANK

.

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

9)

(FOR DUAL

-FUEL INSTALLATION

, SEE NOTE

9)

-

INSTALL APPROPRIATE REGULATOR FOR CURRENT FUEL IN USE

.

-

INSTALLER MUST CHECK WITH LOCAL CODES REGARDING ACCEPTABLE METHOD OF DESIGNING

DUAL GAS PIPING SYSTEM TO PREVENT DIRECT FLOW OF FUEL FROM ONE SYSTEM OF GAS PIPING

INTO ANOTHER

(FOR EXAMPLE

, FROM NATURAL GAS TO PROPANE

, AND VICE VERSA

).

9)

FOR DUAL

-FUEL INSTALLATION

:

FITTINGS

, TO PREVENT INTERFERENCE WITH REMOVAL OF HEATER PANELS

.

WHEN A FLEX CONNECTOR IS FACTORY SUPPLIED

BY AERCO

, IT MUST BE INSTALLED AT THE HOT WATER OUTLET CONNECTION OF THE WATER HEATER

.

ALL PIPING

&

ELECTRIC CONNECTIONS SHOULD BE

6"

AWAY FROM SIDE PANELS

.

LOCATE GAS PRESSURE REGULATOR A MINIMUM OF

2'

FROM HEATER

.